where:
total fresh water flow [m³/h]
q =
nominal LT pump capacity[m³/h]
q
LT =
heat dissipated to HT water [kW]
Φ
=
HT water temperature after engine (91°C)
T
out
=
HT water temperature after cooler (38°C)
T
in
=
Design data:
see chapter Technical Data
Fresh water flow
see chapter Technical Data
Heat to be dissipated
max. 60 kPa (0.6 bar)
Pressure drop on fresh water side
acc. to cooler manufacturer, normally 1.2 - 1.5 x the fresh
water flow
Sea-water flow
acc. to pump head, normally 80 - 140 kPa (0.8 - 1.4 bar)
Pressure drop on sea-water side, norm.
max. 38°C
Fresh water temperature after cooler
15%
Margin (heat rate, fouling)
Fig 9-12
Main dimensions of the central cool-
er.
NOTE
The sizes are for guidance only. These central coolers are dimensioned to exchange
the heat of the engine only, other equipment such as CPP, gearbox etc. is not
taken into account.
Dimension [mm]
Weight
[kg]
P [kW]
Engine type
H
F
E
D
C
B
A
1675
380
1057
330
817
690
193
820
1641
1 x 6L32
Wärtsilä 32 Product Guide - a21 - 7 September 2016
9-15
9. Cooling Water System
Wärtsilä 32 Product Guide
Summary of Contents for WARTSILA32
Page 18: ...This page intentionally left blank...
Page 72: ...This page intentionally left blank...
Page 130: ...This page intentionally left blank...
Page 150: ...This page intentionally left blank...
Page 186: ...This page intentionally left blank...
Page 204: ...This page intentionally left blank...
Page 210: ...This page intentionally left blank...
Page 216: ...This page intentionally left blank...
Page 238: ...This page intentionally left blank...
Page 246: ...This page intentionally left blank...
Page 248: ...This page intentionally left blank...
Page 251: ......
Page 252: ......
Page 253: ......