23.2.3.1 Starting
There are some important properties to be noticed in the start
system of the WECS:
·
Start conditions are all configurable so they may vary de-
pending on the installation,
·
The engine will not start, if either local or remote reset
button isn’t pressed after shutdown.
23.2.3.2 Stopping
There are some important properties to be noticed in the stop
system of the WECS if the stop override signal is included.
·
The emergency stop signal and overspeed shutdown are not
blocked by the stop override signal,
·
The stop override signal is connected via the Relay Module
to the MCU.
23.2.3.3 Start blockings
A start blocking is caused by the following conditions on a marine
engine:
·
low prelubricating oil pressure,
·
turning gear engaged,
·
stop lever in stop position,
·
local/remote switch in local position (blocks the remote start),
·
local/remote switch in remote position (blocks the local start).
On a standard stationary (power plant) engine there are in
addition start blockings for the following conditions (these are all
configurable, i.e. they may vary depending on the installation):
·
engine not preheated (low HT water temp., engine outlet),
·
low fuel oil pressure,
·
low starting air pressure.
If the start blocking is active, it is impossible to perform a start of
the engine. On the Modbus an alarm is given for each start
blocking being active.
23.2.3.4 Shutdowns
An engine shutdown is carried out as a normal stop, i.e. by
activating at the same time the engine pneumatic stop and the
speed governor stop function.
The function of the speed governor stop output in the WECS
system can be configured to correspond to the speed regulator.
The speed governor has an activated or de-activated input for
stopping the engine. The sensors used for shutdown are of ana-
logue type, and the shutdown levels are defined in the WECS
software.
The shutdown is latching, and a shutdown reset has to be given
before it is possible to re-start. Naturally, before this the reason
of the shutdown must be investigated. The reason of any shut-
down will be indicated on the Modbus communication link to the
external systems.
23
Instrumentation and Automation
32-200115/II
23-4
WÄRTSILÄ 32
Summary of Contents for PAAE051728
Page 4: ......
Page 18: ...Appendix B Welding Precautions 200640 00 6...
Page 26: ...01 Main Data Operating Data and General Design 32 200634 01 01 8 W RTSIL 32...
Page 60: ...Appendix A Environmental Hazards 200507 02A 10...
Page 68: ...Page 7 7 Document No 4V92A0645 Rev j...
Page 84: ...03 Start Stop and Operation 32 200402 04 03 12 W RTSIL 32...
Page 98: ...04 Maintenance Schedule 32 200623 01 04 14 W RTSIL 32...
Page 154: ...07 Tightening Torques and Use of Hydraulic Tools 32 200643 01 07 30 W RTSIL 32...
Page 162: ...08 Operating Troubles Emergency Operation 32 200402 01 08 8 W RTSIL 32...
Page 164: ...Specific Installation Data 2005 01 09 2...
Page 178: ...10 Engine Block with Bearings Oil Sump and Cylinder Liner 32 200150 10 14 W RTSIL 32 34SG...
Page 216: ...Appendix A Testing of cylinder tightness 32 200142 A 4 W rtsil 20 32 34...
Page 226: ...13 Camshaft Driving Gear 32 200546 02 13 10 W RTSIL 32...
Page 254: ...15 Turbocharging and Air Cooling 32 200549 10 15 20 W RTSIL 32...
Page 274: ...16 Injection System 32 200627 01 16 20 W RTSIL 32...
Page 280: ...Fuel System 32 200508 07 17 6 W RTSIL 32...
Page 314: ...19 Cooling Water System 32 200050 19 14 W RTSIL 32...
Page 394: ...23 Instrumentation and Automation 32 200115 II 23 60 W RTSIL 32...