WAGO I/O SYSTEM 750 XTR
Appendix 225
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
12.3.2.21.1 Parameter set 2
Table 183: Parameter set 2 of the IO-Link-Masters (IOL_M)
IOL_M
Representative of the IOL_M:
75x-657
Parameterization data length in bytes
Standard parameterization
Structured parameterization
18
22
Parameter
Settings
Description
Scope
Diagnosis
The diagnostic information of the corresponding
channel is
Module
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
Diagnosis
The diagnostic information of the corresponding
port is
Port
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
Multiplier cycle time
The multiplier to get the master cycle time is
Port
0
*)
… 63
•
0
… 63
Master cycle time [ms]
The cycle time in ms results from multiplying the
multiplier parameter and
Port
Multiplier * 0.1
*)
•
0.1
6.4 + Multiplier * 0.4
•
0.4 plus 6.4
32.0 + Multiplier * 1.6
•
1.6 plus 32.0
Operating mode
The operating mode of the corresponding port is
Port
disabled
•
Port disabled.
DI
*)
•
Digital input.
DO
•
Digital output.
IO-Link
•
IO-Link device.
Fragmentation
Fragmentation of the process data of the
corresponding port is
Port
disabled
*)
•
not possible.
enabled
•
possible.
Length input-PI [byte]
Information about the corresponding port
Port
0
*)
•
are not present in the input process image.
1
•
occupy 1 byte in the input process image.
…
...
15
•
occupy 15 bytes in the input process image. Port
Length output-PI [byte]
Information about the corresponding port
0
*)
•
are not present in the output process image.
1
•
occupy 1 byte in the input process image.
…
...
15
•
occupy 15 bytes in the input process image.
*)
Default settings