26
System Description
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
System supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
For 24V system supply input voltage an external fuse, rated max. 2 A, slow
acting, min. 30 VDC shall be used.
Figure 7: System Supply for Fieldbus Coupler/Controller
Only reset the system simultaneously for all supply modules!
Reset the system by switching the system supply simultaneously at all supply
modules (fieldbus coupler/controller and potential supply module with bus power
supply) off and on again.