200 Appendix
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 151: Parameters of the fieldbus coupler as station proxy (FC_SSV)
FC_SSV (slot 0)
750-333
Parameterization data length in bytes
Standard parameterization
Structured parameterization
19
23
Parameter
Settings
Description
Scope
K-Bus transmission stops
•
the process data exchange on the local bus
is stopped, all outputs are switched off after
a module specific monitoring time of 100 ms.
Output image is cleared
•
all outputs are immediately switched off.
Output image is stored
•
all outputs maintain the last status before the
malfunction.
Substitute values are switched
*)
•
all outputs take an individually
parameterizable substitute value.
Response to K-Bus failure
In the event of a malfunction in the internal
communication between fieldbus coupler and I/O
modules, such as, for example no end module
Station
PROFIBUS communication
stops
*)
•
the data exchange with the
PROFIBUS DP master is stopped.
Input image is cleared
•
all input information is set to zero.
Input image is stored
•
the input information immediately before the
fault is maintained.
Startup via DPV1 channel
The cyclic data exchange occurs
Station
disabled
*)
•
immediately after a successful
parameterization and configuration.
enabled
•
only after release of the data exchange on
the acyclic C1 or C2 channel.
Slot assignment
Assigning the slots for acyclic read and write is
performed
Station
DP/V1-compatible
*)
•
according to DP/V1.
S7-compatible
•
according to S7.
IOL diagnosis via
In the event that the diagnostics for the
corresponding port have been released, the
diagnostic results of all IO-Link masters and the
connected IO-Link devices are reported as
Station
Identifier related diagnosis
*)
•
channel-specific diagnostics.
IOL status message
•
IO-Link status message.
*)
Default settings