WAGO I/O SYSTEM 750 XTR
Diagnostics 105
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 50: Blink Code Table for the 'I/O' LED Signaling, Error Code 6
Error code 6: -not used-
Error
Argument
Error Description
Solution
-
Not used
-
Table 51: Blink Code Table for the 'I/O' LED Signaling, Error Code 7
… 8
Error code 7
… 8: -not used-
Error
Argument
Error Description
Solution
-
Not used
-
Table 52: Blink Code Table for the I/O LED Signaling, Error Code 9
Error code 9: “CPU Trap error”
Error
Argument
Error Description
Solution
1
Illegal Opcode
Fault in the program sequence.
1. Please contact the I/O Support.
2
Stack overflow
3
Stack underflow
4
NMI
Table 53: Blink code table fo
r I/O LED signaling, error code 10…11
Error code 10…11: -not used-
Error
argument
Error description
Remedy
-
not used
-
Table 54: Blink Code Table for I/O LED Signaling, Error Code 12
Error code 12
“Initialization error, internal bus”
Error
Argument
Error description
Remedy
n*
Error with parameter
communication during
local bus initialization
1. Switch off the power for the node.
2. Ensure that the nth module with process data is
supplied with power at the field side.
3. Switch the power on.
* The number of light pulses (n) indicates the position of the I/O module.
I/O modules without data are not counted (e.g. supply modules without diagnostics)