WAGO I/O SYSTEM 750 XTR
Commissioning
91
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
8.4.1.1
Physical station design with deactivated parameter “Startup if
expected and actual configuration differ”
Figure 41:
Physical station design with deactivated parameter “Startup if expected and actual
configuration differ” (sample)
If the parameter
“Startup when expected/actual configuration differ” is
deactivated for the fieldbus coupler in the role as a station proxy, the parameter
“I/O module is physical” on the part of the I/O modules receives the settings
“plugged in” or “not plugged”.
To ensure the station powers up correctly, there cannot be any I/O modules
configured as “not plugged” within the physical node.
Diagnostics of existing I/O modules are reported by their configured slot.
The numbers in gray above the node represent the physical DP I/O module slot.
The configured slots are in light blue.
Passive I/O modules ‒ in this case, the 750-602 Supply Module and the 750-600
End Module ‒ that provide no information on the PROFIBUS, are not considered
for the slot assignment.