86
Commissioning
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
Table 37: Identifier bytes
– configuration identifier in the special identifier format (datatype byte)
Byte
Information
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
3/4
Datatype byte(s)
…
16/1
7
\ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - /
1
D
:
Boolean
2
D
:
Integer8
3
D
:
Integer16
4
D
:
Integer32
5
D
:
Unsigned8
6
D
:
Unsigned16
7
D
:
Unsigned32
8
D
:
Float32
9
D
:
VisibleString
10
D
:
OctetString
11
D
:
…
see PI-Guideline 3512 V1.0 September 2006
31
D
:
32
D
:
ArrayOfBoolean
33
D
:
ArrayOfInteger8
34
D
:
ArrayOfInteger16
35
D
:
ArrayOfInteger32
36
D
:
ArrayOfUnsigned8
37
D
:
ArrayOfUnsigned16
38
D
:
ArrayOfUnsigned32
39
D
:
ArrayOfFloat32
40
D
:
…
see PI-Guideline 3512 V1.0 September 2006
79
D
:
80
D
:
ArrayOfBoolean
81
D
:
ArrayOfInteger8
82
D
:
ArrayOfInteger16
83
D
:
ArrayOfInteger32
84
D
:
ArrayOfUnsigned8
85
D
:
ArrayOfUnsigned16
86
D
:
ArrayOfUnsigned32
87
D
:
ArrayOfFloat32
88
D
:
…
see PI-Guideline 3512 V1.0 September 2006
109
D
:
110
D
:
F message trailer with 4 octets
111
D
:
F message trailer with 5 octets
112
D
:
F message trailer with 6 octets
113
D
:
…
see PI-Guideline 3512 V1.0 September 2006
255
D
:
This identifier bytes are saved in the GSD file. When planning, the corresponding
I/O module is selected by the article number in the hardware catalog of the
configuration software.
To simplify the process, available configuration modules are combined in groups
in the following table.