34
System Description
WAGO I/O SYSTEM 750 XTR
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
3.5.4.3
Fusing External
Field supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
The 24 V input voltage for the field supply is provided with an external fuse with
max. 10 A slow, min. 30 VDC, to be secured.
For the external fusing, the fuse modules of the WAGO series 282, 2006, 281
and 2002 are suitable for this purpose.
Figure 14: Fuse Modules for Automotive Fuses, Series 282
Figure 15: Fuse Modules for Automotive Fuses, Series 2006
Figure 16: Fuse Modules with Pivotable Fuse Carrier, Series 281