WAGO I/O SYSTEM 750 XTR
Diagnostics 123
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
9.4.1.1
Fieldbus coupler, slots 0 and 1
Table 73: Fieldbus coupler, slots 0 and 1
Index
Meaning
Service primitives / Data length
[Byte]
00
D
... 07
D
Reserved for expansions
08
D
Configured module setup
MSAC1/2_Read / 2 … 65
09
D
Physical module setup
MSAC1/2_Read / 2 … 65
10
D
... 99
D
Reserved for expansions
128
D
Reserved
129
D
Reserved for expansions
130
D
Fieldbus input image
MSAC1/2_Read / 1 ... 240
131
D
Fieldbus input image
MSAC1/2_Read / 1 ... (244
–240)
132
D
Fieldbus output image
MSAC1/2_Read / 1 ... 240
MSAC1/2_Write / 1 ... 240
133
D
Fieldbus output image
MSAC1/2_Read / 1 ... (244-240)
MSAC1/2_Write / 1 ... (244-240)
134
D
... 139
D
Reserved
140
D
... 253
D
Reserved for expansions
254
D
Enabling of active data
exchange
1)
MSAC1/2_Write / 2
(0x55, 0xAA)
1)
For setting “enabled” of the station proxy– parameter “Startup via
DP/V1 channel
”
9.4.1.2
Complex I/O Modules, Slots 2
… 64
Only for 1-, 2-, 3- and 4-Channel I/O Modules:
Table 74: Complex 1-, 2-, 3- and 4-Channel I/O Modules, Slots 2
… 64
Index
Meaning
'xx00.0000'
Table register 0
...
...
'xx11.1010'
Table register 58
'xx11.1011'
All table registers
'xx11.1100'
Diagnostics data of the channel
'xx11.1101'
Input data of the channel
'xx11.1110'
Output data of the channel
'00xx.xxxx'
Table 0 / channel 0
'01xx.xxxx'
Table 1 / channel 1
'10xx.xxxx'
Table 2 / channel 2
'11xx.xxxx'
Table 3 / channel 3
Only for 8-Channel I/O Modules: