WAGO I/O SYSTEM 750 XTR
System Description
23
750-333/040-000 FC PROFIBUS G2 12MBd XTR
Manual
Version 1.4.0
3.5
Power Supply
3.5.1
Overcurrent Protection
Possible fire hazard due to insufficient overcurrent protection!
In the event of a fault, insufficient overcurrent protection can present a possible
fire hazard. In the event of a fault, excessive current flow in the components can
cause significant overheating. Therefore, you should always dimension the
overcurrent protection according to the anticipated power usage.
The system and field voltage of the WAGO I/O SYSTEMs 750 XTR is supplied on
the head stations and bus supply modules.
For components that work with extra low voltage, only SELV/PELV voltage
sources should be used.
A single voltage source supplying multiple components must be designed
according to the component with the strictest electrical safety requirements.
For components which are only allowed to be supplied by SELV voltage sources,
these requirements are listed in the technical data.
Most components in the WAGO I/O SYSTEM 750 XTR have no internal
overcurrent protection. Therefore, appropriate overcurrent production must
always be implemented externally for the power supply to these components,
e.g. via fuses.
The maximum permissible current is listed in the technical data of the
components used.
System supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
For 24V system supply input voltage an external fuse, rated max. 2 A, slow
acting, min. 30 VDC shall be used.
Field supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
For 24V field supply input voltage an external fuse, rated max. 10 A, slow acting,
min. 30 VDC shall be used.
3.5.2
Isolation
Within the fieldbus node, there are three electrically isolated potentials: