9.3.5
Device Status
The device status includes the required Overhead 7 byte and transmits device
information about the internal status, local bus status or PROFIBUS DP status to
the master or superior controller as required.
Table 60: Device status
Byte-
offset
Information
Meaning
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
0
0
Header byte
Alarm or
status
Length of the module status incl.
header (5-20 bytes)
1
1
0
1
0
0
0
0
0
Message type
Stat
us
Status type = 32 (device status)
2
0
0
0
0
0
0
0
0
Slot
Slot of the station proxy (0)
3
0
0
0
0
0
0
0
0
Status specification
Status
differentiati
on = 00
B
(none)
4
Device status message
Device
status
source
00B:
Internal
status
01B: Local
bus status
10B:
PROFIBUS
DP status
11B:
reserved
Device status value
5
Device status argument
6
Extended device status argument