The table shows the parameterization properties of the 4 and 8-channel analog
input modules with asynchronous diagnostic properties and individual
parameters.
Table 161: Parameters of the 4 (8)-channel analog input modules (AI_PAR)
4AI_PAR (8AI_PAR)
Representatives of the 4AI_PAR:
75x-450
Representatives of the 8AI_PAR:
75x-451
Parameterization data length in bytes
Standard parameterization
Structured parameterization
12
1)
(21
2)
)
16
1)
(25
2)
)
Parameter
Settings
Description
Scope
Terminal is physically
The I/O module process data is
Module
(optionally) not plugged
•
(optionally) set to zero by the fieldbus
coupler.
plugged
*)
•
supplied by the I/O module.
Number format
The format of the number representation
Module
two complement
*)
•
2nd complement.
value/sign
•
Amount plus leading sign.
Siemens S5 format
Raw value range and Resolution according
Module
deactivated
*)
•
standard.
activated
•
Siemens S5-FB250 format.
Notch-Filter
The limiting frequency of the des Filters
Module
deactivated
•
100 Hz
50 Hz
*)
•
50 Hz
60 Hz
•
60 Hz
50/60 Hz
•
50 and 60 Hz
Diagnosis
The diagnostic information of the corresponding
channel is
Channel
disabled
*)
•
not transmitted to the PROFIBUS DP
master.
enabled
•
transmitted to the PROFIBUS DP master.
Sensor type
The sensor is of type
Channel
Pt100 (EN 60751)
*)
•
Thermoresistor Pt100
Ni100 (DIN 43760)
•
Thermoresistor Ni100
Pt1000 (EN 60751)
•
Thermoresistor Pt1000
Pt500 (EN 60751)
•
Thermoresistor Pt500
Pt200 (EN 60751)
•
Thermoresistor Pt200
Ni1000 (TK 6180, DIN 43760)
•
Thermoresistor Ni1000
Ni120 (Minco)
•
Thermoresistor Ni120
Ni1000 (TK5000, DIN 43760)
•
Thermoresistor Ni1000
Ni1000 [TK6180, DIN 43760)
HR
•
Thermoresistor Ni1000
Ni1000 (TK 5000, DIN 43760)
HR
•
Thermoresistor Ni1000
Pt1000 (EN 60751) HR
•
Thermoresistor Pt1000
Potentiometer
3)
•
Potentiometer
Resistor 0R
… 5k (linear)
•
Resistor 0
Ω … 5000 Ω (linear)
Resistor 0R
… 1k2 (linear)
•
Resistor 0
Ω … 1200 Ω (linear)
Connection Type
The connection of the sensor
Channel
deactivated
•
not.
2-wire connection
*)
•
with 2 conductors.
3-wire connection
3)
•
with 3 conductors.
4-wire connection
3)
•
with 4 conductors.
*)
Default settings
1)
Applies to I/O module 75x-450
2)
Applies to I/O module 75x-451
3)