Field Supply
3.5.4.1
Connection
Sensors and actuators can be directly connected to the relevant channel of the
I/O module in 1, 2, 3 or 4 conductor connection technology. The I/O module
supplies power to the sensors and actuators. The input and output drivers of
some I/O modules require the field side supply voltage.
The fieldbus coupler/controller provides field side power (DC 24 V). In this case it
is a passive power supply without protection equipment.
Power supply modules with or without diagnostic capability are available for the
power supply of other field potentials (e.g. 24 VDC, 0 VAC/DC
… 230 VAC/DC,
120 VAC, 230 VAC). The power supply modules can also be used to set up
various potential groups. The connections are connected in pairs to a power
contact.
Figure 8: Field Supply for Fieldbus Couplers/Controllers (Example)
Table 6: Legend for Figure
“Field Supply for Fieldbus Couplers/Controllers”
Position Description
1
Field supply 24 VDC
2
Field supply 0 V
3
Power jumper contacts (potential distribution to adjacent I/O modules)
The field-side power supply is automatically derived from the power jumper
contacts when snapping an I/O module.
The current load of the power contacts must not exceed 10 A on a continual
basis.