Operation
Recycle
The recycle mode is described below.
Pump prime
The pump prime mode is described below.
State
Action or Function
Recycle
The burner will enter the recycle mode if the flame is lost while
the burner is firing.
During the recycle mode:
■
The burner control shuts down the burner.
■
The burner control enters a 60-second delay, then repeats
the ignition sequence.
■
The green flame/recycle light on the control panel flashes.
■
The burner control attempts to recycle each time the flame is
lost, up to three times. If flame is not established after the
third time, the burner control enters the hard lockout state.
To clear the hard lockout fault so a restart can be attempted,
press and hold the reset button for 15 seconds.
State
Action or Function
Pump prime
During the pump prime mode, the cad cell is disregarded,
allowing the technician to prime the pump without having to
jumper the cad cell.
This mode lasts 4 minutes. During this mode:
■
Power is sent to the burner motor/fuel pump.
■
Power is sent to the electrodes.
■
The cad cell is disregarded.
■
The yellow pump prime light illuminates.
To enter the pump prime mode:
1. Prepare the burner for priming.
Do not allow oil to spray
into a hot combustion chamber.
■
Attach a hose over the bleed port fitting.
■
Fully open the pump bleed valve.
■
Use a suitable container to collect the purged oil.
2. Set the temperature controller so there is a call for heat.
3. After the burner starts, press and hold the reset button for 15
seconds until the yellow light turns on, then release the reset
button. The yellow light will turn off, the burner control
powers down the burner, and the burner will then start up
again. At burner startup, press and release the reset button
to enter the pump prime mode. The yellow light will turn on.
To exit the pump prime mode, do one of the following:
■
Set the temperature controller so there is no longer a call for
heat and press the reset button for at least 1 second. The
burner control will return to the standby state.
■
Wait four minutes for the pump prime mode to time out. The
burner control will return to the standby state. The yellow light
will turn off.
Summary of Contents for HI750 Series
Page 6: ...ghi_tx001257gb_FM10 fm 6 Foreword HI750 ...
Page 27: ...HI750 Labels ghi_si000380gb_FM10 fm 27 BB CC FF ...
Page 115: ...wc_tx003699gb_FM10 fm 115 Kubota Genset Genset Maintenance ...
Page 122: ...ghi_td000360gb_FM10 fm 122 Technical Data HI750 Notes ...
Page 142: ......
Page 143: ......