Page 37 of 58
POS-123-*-2030
Typical settings:
Command
Input
Description
AIN:X 1000 1000 0 V
0… 10 V
Range: 0… 100 %
AIN:X 10 8 1000 V
OR
AIN:X 1000 800 1000 V
1… 9 V
Range: 0… 100 %; 1 V = 1000 used for the offset and
gained by 10 / 8 (10 V divided by 8 V (9 V -1 V))
AIN:X 10 4 500 V
OR
AIN:X 1000 400 500 V
0,5… 4,5
V
Range: 0… 100 %; 0,5 V = 500 used for the offset and
gained by 10 / 4 (10 V divided by 4 V (4,5 V -0,5 V))
AIN:X 20 16 2000 C
OR
AIN:X 2000 1600 2000 C
OR
AIN:X 1250 1000 2000 C
4… 20mA
Range: 0… 100 %
The offset will be compensated on 20 % (4 mA) and the
signal (16 mA = 20 mA
– 4 mA) will be gained to 100 %
(20 mA).
Each of this parameterization for 4… 20 mA is setting the
range to 0… 100 %.
5.9 Process data
Command
Description
Unit
WA
W
V
X
E
C
U
IA
IB
Demand value (input signal)
Demand value (according to the profile generator)
Speed input
Actual value
Error value
Output of the controller
Output signal of the module
Solenoid current A
Solenoid current B
mm
mm
%
mm
mm
%
%
mA (P Version only)
mA (P Version only)
The process data are the variables which can be observed continuously on the monitor or on the oscilloscope.