Page 33 of 58
POS-123-*-2030
5.7.4
OFFSET (Zero correction)
Command
Parameters
Unit
Group
OFFSET
x
x= -4000… 4000
0,01 %
STD
This parameter is entered in 0,0 1% units.
The offset value is added to the output value. Valve zero offsets can be compensated with this parameter.
5.7.5
SIGNAL:U (Type and polarity of the output signal)
Command
Parameter
Unit
Group
SIGNAL:U x
x=
U+-10
I4-12-20
U-+10
I20-12-4
-
EXP
This command is used to define the output signal (voltage or current) and to change the polarity
12
.
Differential output ± 100 % corresponds with ±
10 V (0… 10 V at PIN 15 and PIN 16).
Current output ± 100 % corresponds with
4… 20 mA (PIN 15 to PIN 12). 12 mA (0 %) = center point of the
valve.
An output current of << 4 mA indicates an error and the module is disabled. The current input of
the proportional valves should be monitored by the valve. The valve have to be deactivated in case
of < 4 mA input signal. Otherwise the EOUT command can be used to get a defined output signal.
12
The older POL command is removed.