Cycle
. On how long passed time the
system will do the cleaning. The time is in
minutes. The setting is from 10 to 1440
minutes.
360 min.
For instance:
We can set on Cycle 360 minutes,
whereas on Number of Repetitions 3
times.
On this time of 360 minutes passing, Fire-
grate & Fire Tubes Clean gets active, and
there are 3 rotations done.
Interim Purge
Period
Here one cans et the time from 100 to
4000 seconds, in 10 seconds. This setting
is about how long it will take the fireplace
to launch cumulate residue clean.
The time to set should be the sumtotal of
the operation of the screw conveyor. This
way one can calculate the amount of
pellets after which there should follow a
cleaning process!
1800 sec.
Fan 100%
How long an Interim Purge will last.
The time is set within the range of 2 to
100 seconds, in 1 second.
12 sec.
Here one can restore the factory settings of
the control unit.
Outputs Test
(Manual Mode).
Activates all outputs at the same time
Pump
Heater
Smoke Fan
Screw Conveyor
Ashes Clean
Outside Feed
Tubes Clean
Fire-grate Clean
12. Instruction manual.
12.1. Wood pellets loading.
The capacity of the pellet fuel hopper is 120 kg. The opening for charging the hopper is with dimensions 350 х 620 mm.
For proper appliance operation, it is important the person who installed the unit to comply with the following procedure in the
initial ignition. To load and spend 15 kg of wood pellets. This will allow loading of the supply system. Load a new supply of 15 kg
wood pellets.