INSTRUCTION MANUAL 

for installation and operation of pellet boiler

 CLASSIC 40C

 

 

 

19

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

 

Cycle

. On how long passed time the 

system will do the cleaning. The time is in 
minutes. The setting is from 10 to 1440 
minutes. 

 

360 min. 

For instance: 
We can set   on Cycle 360 minutes, 
whereas on Number of Repetitions 3 
times. 
On this time of 360 minutes passing, Fire-
grate & Fire Tubes Clean gets active, and 
there are 3 rotations done.

  

 
 
 
 
 
 

Interim Purge 
Period

 

Here one cans et the time from 100 to 
4000 seconds, in 10 seconds. This setting 
is about how long it will take the fireplace 
to launch cumulate residue clean. 
The time to set should be the sumtotal of 
the operation of the screw conveyor. This 
way one can calculate the amount of 
pellets after which there should follow a 
cleaning process! 

1800 sec. 

Fan 100% 

How long an Interim Purge will last. 
The time is set within the range of 2 to 
100 seconds, in 1 second. 

12 sec. 

 
 
 

 
 

Here one can restore the factory settings of 

the control unit. 

 

                        
                    

Outputs Test        

                (Manual Mode).

 

 
 
 
 
 
 
 
 
 
 
 
 
 

           
 
             

Activates all outputs at the same time 

 
 

 

Pump 

 

Heater 

 

Smoke Fan 

 

Screw Conveyor 

 

Ashes Clean 

 

 

 

Outside Feed 

 

Tubes Clean 

 

Fire-grate Clean 

 

 

12. Instruction manual. 

12.1. Wood pellets loading. 

The capacity of the pellet fuel hopper is 120 kg. The opening for charging the hopper is with dimensions 350 х 620 mm. 
For proper appliance operation, it is important the person who installed the unit to comply with the following procedure in the 
initial ignition. To load and spend 15 kg of wood pellets. This will allow loading of the supply system. Load a new supply of 15 kg 
wood pellets. 

Summary of Contents for CLASSIC 40C

Page 1: ...INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C...

Page 2: ...11 2 CONTROL PANEL DESCRIPTION 13 11 2 1 MAIN USER CONTROL PANEL 13 11 2 2 TYPES OF MODES OF THE CONTROL UNIT 14 11 2 3 MAIN MENU 14 11 2 5 SERVICE TECHNICIAN SETTINGS 18 12 INSTRUCTION MANUAL 19 12...

Page 3: ...act with fire or hot surfaces Pellet boiler is equipped with safety components that guarantee automatically shut down in case of failure of any of its components Safety components are activated withou...

Page 4: ...hould not be placed back in the pellet fuel hopper 3 Technical data and dimensions Fig 1 Button with safety cover to reset the thermo limiter Main switch with integrated socket for power cable out for...

Page 5: ...construction of the pellet boiler allows mounting of the ashtray in left side or right side 1 1 1 Pellet boiler 2 Bracket 3 Screw 6 12 DIN 912 2 pcs 4 Washer 6 DIN 125 6 pcs 5 Screw 6 x 16 DIN 912 2 p...

Page 6: ...ximum draught 12 Duration of combustion at nominal heat output at reduced heat output 14 h 47 h Fuel consumption minimum maximum 2 56 8 51 Type and dimensions of fuel Wood pellets 6 mm length 25 mm cl...

Page 7: ...tat of the pellet fuel hopper Placed on the auger housing near the pellet fuel hopper It interrupts feeding of the pellets if its temperature reaches 85 C also interrupts the indication of the water t...

Page 8: ...er works with wood pellets These are cylindrical granules made of pressed wood whose combustion is controlled by an electronic control system The heat from the combustion process is given to the fluid...

Page 9: ...ts can cause blockage of the auger and to stop the operation of the pellet boiler IF PELLET BOILER IS BLOCKED THE REASON WILL APPEAR ON THE DISPLAY AND IT WILL BE SAVED Using wood pellets of poor qual...

Page 10: ...t wind Chimneys Pellet boiler works constantly with a fume extractor and pressure in the flue pipes and chimney It is forbidden the flue gases to be discharged directly from the pellet boiler through...

Page 11: ...volume ensures good and smooth operation of the appliance and Pellet boiler MUST NEVER OPERATE without liquid in the heating system and under pressure less than 1 bar Failure to comply with these con...

Page 12: ...with the standard circulation pump and at the same time to keep the same level of power output and performance The pump operates on the principle of proportional pressure Technical data Max pumping 6...

Page 13: ...g the coating The flavor which is obtained as a result of the drying of the paint disappears after a few hours Ventilate the room where is located the pellet boiler If as a result of overheating or du...

Page 14: ...he icon would start the screw conveyor for 10 seconds When this time is over the screw conveyor stops again and waits until a new icon click is done The icon would only be visible in Ready Mode wherea...

Page 15: ...re one can set the Upper Buffer Bumper Sensor and the Lower Buffer Bumper Sensor operation temperature hermostat The Indoor Sensor can be either switched on or off Note It is possible that this settin...

Page 16: ...three options The first one is Switch the Timer ON If set active the fireplace would automatically transfer to Timer Mode The second one is Delayed Start To set this one active it is important that th...

Page 17: ...rst level is Installer The second level is Service Technician The third level is Delete Errors with a password 7777 The fourth password is 2468 and serves to unlock the display The display can be lock...

Page 18: ...erature On Here one can set the Water Temperature which the pump switches on at 45 0 C Hysteresis 2 C 10 C This is the thermal lag at which the pump will stop operating I e if it has been set ot switc...

Page 19: ...is way one can calculate the amount of pellets after which there should follow a cleaning process 1800 sec Fan 100 How long an Interim Purge will last The time is set within the range of 2 to 100 seco...

Page 20: ...chamber If necessary the cleaning time and power output can be adjusted in menu Cleaning When the time is over the device transfers to Fuel Mode In this mode there is a countdown as well The screw co...

Page 21: ...t one is for the Time Clock which has been preset to 600 seconds to run out and only after that the water heater temperature is checked to have decreased down below the preset one these two events hav...

Page 22: ...ition system Clean and check the electronic control system Check all electrical cables Clean the pellet fuel hopper and check auger to loosen the screw and the gear motor Check and if needed replace t...

Page 23: ...e has to drop below this value Unsuccessful Ignition Failed ignition The alarm is shown if during operation of the stove the fume outlet sensor detects lower than the set temperature When the alarm is...

Page 24: ...on manual What is needed to prepare and do before installing the pellet boiler Chimney with a diameter of at least 100 mm Opening for fresh air with a cross section not less than 80 cm 2 1 1 4 connect...

Page 25: ...ure in the heating system is reached The installer must make the appropriate setting How often should you clean the combustion chamber Before each ignition of the pellet boiler but only when it is tur...

Page 26: ...05 2020 INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C 26...

Page 27: ...allowed penetration of foreign substances in the firebox or hopper Do not use combustible materials to clean soot in the chimney Turn off the pellet boiler from the grid circuit before cleaning or ser...

Page 28: ...hot water outlet 9 Electronic control system set 10 Control panel 11 Circulation pump WITA DELTA MIDI 60 32 180 12 Glass 4 x 100 x 100 mm 13 Combustion chamber retort set 192 00 14 00 14 Handle 15 Fir...

Page 29: ...g population For other countries please contact you dealer Any warranty repair of the pellet boiler is recorded in the diary of warranty Warranty of the pellet boiler is NOT VALID in the following cas...

Page 30: ...05 2020 INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C 30 DIARY for repairs under warranty Company Receipt date Type of repair Delivery date Carried out...

Page 31: ...05 2020 INSTRUCTION MANUAL for installation and operation of pellet boiler CLASSIC 40C 31...

Page 32: ...NUAL for installation and operation of pellet boiler CLASSIC 40C 32 Victoria 05 Ltd 1B Ivan Momchilov Str 5100 Gorna Oryahovitsa Republic of Bulgaria phone 359 618 60282 fax 359 618 60200 e mail info...

Reviews: