05.2020
INSTRUCTION MANUAL
for installation and operation of pellet boiler
CLASSIC 40C
18
1.
Type.
- No feed. Meaning that no
outside pellets feed is on.
- Vacuum. Pellets Feed from
an outside bunker, via a
vacuum cleaner.
- Screw Conveyor. Pellets
Feed via an outside source,
via an outside screw
conveyor.
Option
2
. Time.
Via this parameter one can
set how long the feed would
take. On unsuccessful feed a
“Pellets Missing” Alarm is
on.
Option
Sec. (Pellet feed via
vacuum cleaner)
Min. (Pellet feed
through external
auger
3.
Daily Timer.
- Via this parameter one can
set when within the twenty-
four hours the system for
outside pellets feed is to
operate.
11.2.5. Service Technician Settings.
`
Параметър
Factory settings
Temperature On
Here one can set the Water Temperature,
which the pump switches on at.
45
0
C
Hysteresis (2°C ÷ 10
°
C)
This is the thermal lag at which the pump
will stop operating. I.e. if it has been set ot
switch on at 60°С, it will stop at 55°С, if
the hysteresis is 5°С
.
5
0
C
Initial Purge
In Initial Purge the duration of the
operation of the smoke fan can be set to
100% in seconds in the Start Mode.
60 sec.
Ashes Clean
Here we can set how long the Ashes
Disposal System to the outside Ashes
Bunker will be cleaning. The setting is in
seconds within 10 up to 300.
150 sec.
Automatic Clean
In Auto Clean there two parameters.
Number of repetitions
. How many times
the Fire-grate & Fire Tubes Clean System
will start.
For instance:
We can set on Cycle 60 minutes, whereas
on Number of Repetitions 3 times.
On this time of 60 minutes passing, Fire-
grate & Fire Tubes Clean gets active, and
there are 4 rotations done.
3