05.2020
INSTRUCTION MANUAL
for installation and operation of pellet boiler
CLASSIC 40C
11
Fig.4.
Fig.5
А -
Insulated metal chimney.
В -
minimum height of the vertical section 1.5 m, as the end of the chimney has to be completed in accordance with Fig. 5
С -
Incoming outside air through the section with minimum cross section of 80 сm
2
.
Е -
Incoming outside air through the section with minimum cross section of 80 cm.
D -
Metal pipe in masonry chimney.
Hydraulic connections:
Integral boiler the pellet boiler has a capacity of 90 liters. This volume ensures good and smooth operation of the appliance
and
Pellet boiler MUST NEVER OPERATE without liquid in the heating system and under pressure less than 1 bar. Failure
to comply with these conditions leads to damage!
It is obligatory to install the pellet boiler with three way valve. This helps to prevent condensation and expand its
life.
A.
Outlet hot water
B.
Inlet cold water
1. Pellet boiler
2. Integral boiler
3. Control unit
4. Automatic air vent
5. Hydraulic safety valve 3 bar
6. Filling/empting valve
7. Buffer tank
8. Sensor “buffer up”
9. Heat consumers
10. Sensor “buffer down”
11. Three-way mixing valve thermostatic
12. Stopcock
13. Filter
14. Closed expansion vessel 1.5 bar
15. Drainage
16. Built-in circulation pump