69

Viconics Technologies Inc.

                                                  

www.viconics.com

   |   

[email protected]

|   

                  

   

Tel: (514) 321-5660

   |   

Fax: (514) 321-4150

028-0427-11 

                                                                                                                                     October 2018

Y1 status

BO1 aux. out

Off

Off

Off

G fan status

Y2 status

Off

1/2 Test Outputs

W1 status

Off

W2/OB status

Off

TEST OUTPUTS 1/2

Note 1: 

The Test Outputs screen allows manual override of  specified outputs. After any output state is overridden, the command is 

cancelled after 1 minute of  screen inactivity (auto exit to main screen) or when page is exited.

Note 2: 

Use high caution when manually enabling outputs so as to not cause damage to equipment. It is the responsibility of  the 

Installer or Service Contractor to maintain a safe operation environment during usage.

Note 3: 

These parameters can also be changed via BACnet and the changed parameter background will turn red to indicate the 

parameter’s value had been overridden. The overridden value remains even if  the user exits the main screen

Summary of Contents for VT8600 Series

Page 1: ...1 Version 11 VT8600 Series User Interface Guide Rooftop Unit Heatpump and Indoor Air Quality Controller ...

Page 2: ... 13 Fan Mode Settings 13 Heating Only Configuration 14 Setpoint Adjustment Cooling 14 Setpoint Adjustment Heating 15 Other Functions 15 Customizable Color Options 16 Network Settings 18 ZigBee Network Settings 22 BACnet Network Settings 22 Modbus Network Settings 24 Configuration Screens 26 Setpoint Screens 49 Display Screens 54 Service View Screens 59 Test Outputs Screens 70 Language Selection Sc...

Page 3: ...SECTION 1 Introduction ...

Page 4: ...r XXXX Parameter XXXX Parameter Adjustable parameter Some parameters appear only when Zig Bee wireless communication module is installed or if a LUA script is uploaded Change Value Previous screen Next screen Return to pre vious menu Notes 1 When any change is made to a parameter the value is permanently saved in the database when the next parameter is selected or another screen is opened This eve...

Page 5: ... or a different image is uploaded and selected to be dis played To minimize and prevent image retention it is recommended to select the Screen Save setting on the Standby screen selection from the setup menu Display 1 2 This setting switches the display during periods of inactivity from the Home Screen It is recommended to use a black or medium gray image or one with light color contrasts as the s...

Page 6: ...HMI Display and Set up ...

Page 7: ...er HMI is configurable and allows display functions such as Date Time Humidity Outdoor Temperature and Setpoint to be enabled or disabled by setting various parameters Time System Status Fan Status Increase Temperature Setpoint Actual Setpoint Decrease Temperature Setpoint Indoor Humidity Outdoor Temperature Indoor Temperature Occupancy Status Help Language Selection Temperature Units Fan Mode Sys...

Page 8: ...pt shows to prevent access to device configuration components Enter Set up Screen SET UP 1 2 Return to previous menu 1 2 Setup Network Configuration Setpoints Display Service view Test Outputs Discover Mode shows wireless ZigBee network Icon not shown if ZigBee communication module not installed BACnet MS TP Modbus and ZigBee network settings ZigBee network settings appear only if a communication ...

Page 9: ...028 0427 11 October 2018 SET UP 2 2 2 2 Setup Clock Schedule LUA Wireless Language Selection ADR Automatic Demand Response LUA scripting shows only if LUA script uploaded Wireless Ecosystem settings shows only if ZigBee communication module installed Select language Set clock schedule and occupancy ...

Page 10: ...SECTION 2 Customized Screens ...

Page 11: ...nguage User help menu Setpoint adjustment User help menu Parameters are model dependent and may not appear on certain models Fully locked interface with no user settings Setpoint adjustment System mode setting User help menu Setpoint adjustment System mode setting Fan mode setting Local unit scale adjustment User help menu Setpoint adjustment System mode setting Fan mode setting unoccupied mode ov...

Page 12: ...ide Setpoint adjustment System mode setting Unoccupied mode override User help menu Parameters are model dependent and may not appear on certain models Note The day night setback button appears only in unoccupied mode from 7 to 11 in HMI Commercial If UI17 input is configured as override the day night setback button does not show 8 Commercial 9 Commercial 10 Commercial 11 Commercial Commercial Use...

Page 13: ...ation is allowed System mode Cool Cool Room Controller only satisfies Cooling demands Heating demands are ignored Dehumidification is allowed System mode Heat Cool Room Controller only satisfies Heating demands Cooling demands are ignored Dehumidification is allowed Fan Mode Settings Fan Mode Setting Mode Significance and Adjustments Fan mode ON On Fan is on continuously even when system mode is O...

Page 14: ...n sequence of operation is set to either heating on or cooling only Cooling mode or cooling only sequence of operation Heating only Configuration Setpoint Adjustment for Cooling Mode In Cooling mode the setpoint displayed in the bar is the current occupied cooling setpoint During occupied setpoint adjustment the large digits are temporarily used to show occupied cooling setpoint while it is adjust...

Page 15: ...Setpoint The actual setpoint is dependent on the last effective demand heating or cooling The setpoint on top of the red line represents the actual occupied heating setpoint The differential between the occupied heating and cooling setpoint is defined by the minimum deadband configuration parameter Normal temperature display resumes after setpoints are adjusted and the actual occupied heating and ...

Page 16: ... Inc www viconics com sales viconics com Tel 514 321 5660 Fax 514 321 4150 028 0427 11 October 2018 Customizable Color Options 2018 04 18 12 54 PM 2018 04 18 12 54 PM 2018 04 18 12 54 PM 2018 04 18 12 54 PM 2018 04 18 12 54 PM ...

Page 17: ...Network Screens ...

Page 18: ...Read Only Wired protocol BACnet MS TP or Modbus PARAMETER DETAILS Configuration Parameters Default Value Significance and Adjustments Optional prot Read Only Optional Protocol Requires installation of optional ZigBee Pro communication module None No ZigBee card detected ZigBee ZigBee card detected Display Readings None or ZigBee Wired protocol Default value BACnet Wired Protocol None No wired prot...

Page 19: ...rdinator permit join must be set to ON Choices Coordinator or Router Pan ID Default value 0 ZigBee Pan ID Personal Area Network Identification that links specific Room Controllers to specific ZigBee coordinators For every Room Controller reporting to a coordinator set the SAME PAN ID value both on the coordinator and the Room Controller NOTE The default value of 0 is NOT a valid PAN ID NOTE For Ro...

Page 20: ... 25 is recommended Range 10 to 25 Network status Read Only ZigBee Network Status Shows the current status of the ZigBee network No NWK ZigBee configured but no network joined Joined ZigBee network joined Online Communicating Exchanging data Display Readings No NWK Joined Online Permit join Default value On Permit Join Changing this value to Off on the Coordinator prevents any new ZigBee devices fr...

Page 21: ...lue Significance and Adjustments IEEE address Read Only IEEE Address The extended IEEE address MAC address is a unique worldwide identifier of the VCM Module Short address Default value 0 Read Only ZigBee Short Address ZigBee Pro short address The unique address is generated once device joins a ZigBee network ZigBee rev Read Only Communication Module Revision Number Shows the revision number of th...

Page 22: ... 254 Network units Default value SI Measurement Units Network units transmitted over the BACnet network NOTE Use the Temperature scale parameter to change the display units locally on the Room Controller Imperial Network units shown as Imperial units SI Network units shown as International Metric units Choices Imperial or SI Network lang Default value English Network Language Network language obje...

Page 23: ...COM address of the Room Controller For example the instance number of a VT8600A5B00 with a COM address of 57 is generated as 86057 The default instance number appears first To change the instance number use number pad and press Accept and save Tap R icon to reset to automatic instance addressing 0 8 3 0 0 5 7 2 2 BACnet instance Instance number of Room Controller Accept and save Reset to automatic...

Page 24: ...alues not recommended for Modbus Default value of 254 disables Modbus communication for the Room Controller Range 0 to 254 Network units Default value SI Measurement Units Network units transmitted over the BACnet network NOTE Use the Temperature scale parameter to change the display units locally on the Room Controller Imperial network units shown as Imperial units SI network units shown as Inter...

Page 25: ...Configuration Screens ...

Page 26: ...n via a dry contact Motion NO and Motion NC Advanced PIR occupancy functions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Window Forces system to disable any current heating or cooling action by Room Controller when window is open Fan lock When G Fan output is activated if this input is not activated after 10 seconds the Room Controller disables Heat and Cool outputs and...

Page 27: ...ion associated with input however input can be used for remote network monitoring CO2 Using the CO2 level measured by a wired CO2 sensor 0 2000 ppm 0 10 Vdc the Outside Air damper Econo will modulate between Econo min pos to Econo max pos following the Min CO2 and Max CO2 setpoints Choices None or CO2 Smart recovery Default value Off Enable Smart Recovery Off No smart recovery The occupied schedul...

Page 28: ...ode button functionality and hides shows temperature setpoints on main screen Normal System mode button switches between Off Auto Cool and Heat Also displays temperature Setpoints on main screen Off Auto System mode button switches between Off and Auto Hides temperature Setpoints on main screen NOTE Setting Mode button to Off Auto forces the Setpoint func parameter to Attach SP Choices Normal or O...

Page 29: ...ng stages terminals W1 W2 are solicited will not be energized The fan is controlled by the equipment fan limit control Valid only for Auto fan mode On fan mode leaves the fan always on For multi stage models fan control applies to W1 W2 Choices On or Off Fan delay Default value On Fan Delay On fan mode will leave the fan always on and extends fan operation by 60 seconds after the call for heating ...

Page 30: ...iff Range 1 to 5 F 0 5 to 2 5 C Power up delay Default value 10 seconds Power up Delay On initial power up of the Room Controller there is a delay before any operation is authorized fan cooling or heating This can be used to sequence the start up of multiple Room Controllers in one location Range 10 to 120 seconds Occupancy src Default value Motion Occupancy Source Motion occupancy status is recei...

Page 31: ... which the Room Controller unoccupied mode and setpoints become active Note Default value of 0 0 hours disables the unoccupied timer This prevents the Room Controller from being able to switch from stand by mode to unoccupied mode when PIR functions are used Range 0 0 to 24 0 hours 0 5 hour increments Temp occ time Default value 2 hours Temporary Occupancy Time The time the Room Controller stays i...

Page 32: ...e Green Power device as the source for the room temperature Note The Room Controller uses the internal temperature sensor only if UI20 RS terminal is empty If a valid temperature sensor is connected to UI20 terminal the Room Controller will automatically disable its internal sensors Internal WL1 to WL10 WL GP and use the remote sensor as the control point Disconnecting the sensor or if the sensor ...

Page 33: ...ts a higher accuracy of control at the expense of wearing mechanical components faster Note The CPH does not limit the number of Cycles Per Hour It is limited by the Anti short cycle parameter 4 CPH is typical for Rooftop applications Range 3 to 4 CPH Heating CPH Default value 4 CPH Heating Stages Cycles per Hour CPH is used to modulate On Off outputs controlling equipment such as compressors When...

Page 34: ...2 NC Occ or St By Contact Opened Unoccupied Contact Closed Choices NO or NC Anti short cycle Default value 2 minutes Anti Short Cycle Time Minimum On time and minimum Off time of operation time for stages IMPORTANT anti short cycling can be set to 0 minutes for equipment that possess their own anti cycling timer Do not use this value unless the equipment is equipped with an internal timer Failure ...

Page 35: ...nd used by Room Controller PI control loop Note Default value of 3 gives satisfactory operation in most normal installation cases The use of a superior proportional band different than the factory value is normally warranted in applications where Room Controller location is problematic and leads to unwanted cycling of the unit A typical example is a wall mounted Room Controller installed between r...

Page 36: ...es 0 1 or 2 stages Cool stages Default value 2 stages Number of Cooling Stages Sets number of Cooling Stages 1 Stage Only Y1 BO3 terminal is used Y2 is disabled 2 Stages Both Y1 BO3 and Y2 BO2 terminals are used in sequence Choices 1 or 2 stages Econo config Default value Off Economizer Configuration Enables or disables the economizer functionality On Economizer activated Off Economizer deactivate...

Page 37: ...ng setpoint Off Applies when the mixed air temperature sensor is installed after the mechanical cooling refrigeration coils In this case mechanical cooling never operates at the same time as free cooling On Applies when the mixed air temperature sensor is installed before the mechanical cooling refrigeration coils in the mixing plenum In this case mechanical cooling is allowed when the free coolin...

Page 38: ...r via a BACnet front end network Range 15 F to 120 F 26 C to 49 C Cool lockout Default value 40 F 40 C Cooling Lockout from Outside Air Temperature Disables mechanical cooling operation when Outdoor Temperature is lower than the Cool Lockout value The Outdoor Temperature value could be received from a sensor connected directly to the Room Controller UI23 or via a BACnet front end network The Econo...

Page 39: ...r via a BACnet front end network Note valid only if Heat Stages parameter is set to 0 Analog Heat on UO11 Range 15 F to 120 F 26 C to 49 C FA Range Default value 0 CFM Fresh Air Range Sets the upper limit reading range of the airflow measuring station eg for 0 1 000 CFM station set FA Range to 1 000 If set to 0 CFM this function is disabled and the fresh air damper control will be based on the Min...

Page 40: ...ments Econo min pos Default value 0 Economizer Minimum Position Minimum Outside Air damper position when Room Controller is in Occupied Standby or Override mode and Fan status is ON If Room Controller is in Unoccupied mode and or the Fan is Off Outside Air damper position goes to 0 Range 0 to 100 Econo max pos Default value 100 Economizer Maximum Position Maximum Outside Air damper position when R...

Page 41: ...be switched to 0 10 Vdc control logic The following chart indicates the appropriate equivalent damper positions for use with 2 10Vdc actuators Outside air percent age 0 5 10 15 20 25 30 35 40 45 50 Setting for 0 10 Vdc Actuator 0 5 10 15 20 25 30 35 40 45 50 Setting for 2 10 Vdc Actuator 20 24 28 32 36 40 44 48 52 56 60 Outside air percent age 55 60 65 70 75 80 85 90 95 100 Setting for 0 10 Vdc Ac...

Page 42: ...ide airflow setpoint Effective only in Occupied Standby or Override mode and Fan status is ON If FA Range is set to value other than 0 CFM the fresh air damper position control will be based on the Min Max CO2 and Min Max Fresh Air values Range 0 to 20 000 CFM 10 increments The value set cannot exceed the value of FA Range parameter Min CO2 Default value 800 ppm Minimum CO2 Minimum CO2 level setpo...

Page 43: ...which the auxiliary heat is cut off If the temperature exceeds this value only the heat pump is used to maintain the heating setpoint NOTE Function enabled only if outside air temperature value is populated not 40 F C The Outdoor Temperature value could be received from a sensor connected directly to the Room Controller or via a BACnet front end network Range 34 F to 90 F 1 0 C to 32 0 C Low BP De...

Page 44: ... low balance point the deadband gets eliminated and the auxiliary heat maintains the true heating setpoint alone Choices Comfort or Economy Rev valve Default value O Reversing Valve Operation Heat pump reversing valve operation O energize valve in cooling operation B energize valve in heating operation Choices O or B Comp interlock Default value Off Compressor Auxiliary Interlock Sets the operatio...

Page 45: ... password Default value 0 User Password Sets a protective access password to prevent User unauthorized access to main screen adjustments A default value of 0 will not prompt for a password Range 0 to 9999 Schedule menu Default value Enabled Schedule Menu Toggles activation of schedule menu direct access Enabled Schedule Menu is directly accessible from the main screen via a touch in the upper corn...

Page 46: ...he actual displayed outdoor temperature Range 5 0 F 2 5 C Calib humid Default value 0 0 RH Calibrate Humidity Sensor Offset that can be added or subtracted to actual displayed humidity Range 15 0 RH RH sensor Default value Internal Relative Humidity Sensor Sets the source of the indoor room humidity This parameter allows the user to designate either the Room Controller only models supporting humid...

Page 47: ...ion parameters default value Significance and adjustments Erase all Default value No Erase All Accepting Yes for both and then tapping Push to accept returns all values to the factory default settings with the exception of the following COM address Network Units Network Language Baud Rate BACnet Instance Device Name Screen Contrast Lua Script Note Node type in ZigBee Pro menu returns to default va...

Page 48: ...Setpoints Screens ...

Page 49: ...used by the Room Controller when in Unoccupied mode Range 54 to 100 F 12 0 to 37 5 C Standby cool Default value 78 F 25 5 C Standby Cooling Setpoint Cooling Temperature setpoint used by the Room Controller when in Standby mode Range 54 to 100 F 12 0 to 37 5 C Occ cool Default value 75 F 24 C Occupied Cool Setpoint Cooling Temperature setpoint used by the Room Controller when in Occupied or Overrid...

Page 50: ...t Default value 69 F 20 5 C Standby Heating Setpoint Heating Temperature setpoint used by the Room Controller when in Standby mode Range 40 to 90 F 4 5 to 32 0 C Unocc heat Default value 62 F 17 C Unoccupied Heating Heating Temperature setpoint used by the Room Controller when in Occupied or Override mode Range 40 to 90 F 4 5 to 32 0 C ...

Page 51: ... is in unoccupied mode any movement detected by a wired wireless or local PIR sensor changes the occupancy mode to occupied modes and uses the Default Heating Setpoint as the new occupied setpoints NOTE This functionality is only valid when Stand by mode Offset and Setpoint Func is set to Attached Range 65 to 80 F 18 5 to 26 5 C Min deadband Default value 3 F 1 5 C Minimum Deadband Temperature off...

Page 52: ...aximum Occupied Unoccupied Standby and Override Cooling setpoint adjustment Range 54 to 100 F 12 0 to 37 5 C Supply air SP Default value 55 F 12 C Supply Air Setpoint Free cooling supply air setpoint when economizer mode is enabled Range 50 to 90 F 10 0 to 32 0 C Dehum SP Default value 50 RH Dehumidification Setpoint Used only if dehumidification sequence is enabled Range 30 to 95 RH ...

Page 53: ...Display Screens ...

Page 54: ...n parameters Default Value Significance and Adjustments User HMI Default value 0 User HMI Sets layout of icons on the home screen for various applications Refer to Customized screen for more information Range 0 to 12 Color Default value White HMI Color Change background color of the display screen Choices White Green Blue Grey or Dark Grey Main display Default value Temp Main Display Shows tempera...

Page 55: ...ter 30 minutes only in occupied or override mode Screen saver Standby image displays after 150 seconds Screen turns off after 30 minutes only in unoccupied or standby mode Choices No Yes Occupied Only or Screen Saver Lock screen Default value No Lock Screen Prevents the user from accessing the Room Controller until a password is entered Screen lockout starts 150 seconds after no activity on the Ro...

Page 56: ... Japanese Norwegian Polish Portuguese Slovak Swedish and Turkish Units Default value C Temperature Scale Changes the local display units Refer to Network Units to change the network units broadcasted over the network Choices C for SI or F for Imperial Low backlight Default value 60 Low Backlight Sets display backlight intensity This feature is activated screen dims 150 seconds after no activity on...

Page 57: ... RH display Default value Disabled Relative Humidity Shows humidity level in room in RH On Display RH Off Do not display RH Choices Enabled or Disabled CO2 display Default value Disabled CO2 Levels Display Shows carbon dioxide level in room in ppm On Display CO2 level Off Do not display CO2 level Choices Enabled or Disabled ...

Page 58: ...Service View Screens ...

Page 59: ...urrently installed on Room Controller Upgrading to a newer Firmware version deletes the previous Firmware version however it is possible to set the Room Controller to an earlier Firmware version with the Uploader Tool Room temp Read Only Room Temperature Shows the current room temperature The user can set one of the following temperature inputs to act as the source for the room temperature s prese...

Page 60: ...efault Value Significance and Adjustments Effective occ Read Only Effective Occupancy Shows as occupied unoccupied standby or override Display Readings Occupied Unoccupied Override and Standby PI cool demand Read Only Cooling Demand Display Readings 0 100 PI heat demand Read Only Heat Demand Display Readings 0 100 Cool dem limit Read Only Outdoor Temperature Display Readings 0 100 Heat dem limit R...

Page 61: ...on No 2 Shows status of input Display Readings Activated or Not Activated UI19 analog Read Only Universal Input Configuration No 3 Shows scaled percentage level of wired CO2 sensor 0 0ppm 100 2000ppm Display Readings 0 100 Airflow level Read Only Airflow level Shows the amount of air in cubic feet minute that flows through a particular device Display Readings 0 100 Zigb PIR inst Read Only ZigBee P...

Page 62: ...ors Display Readings On or Off Service alarm Read Only Service Alarm Shows On if there is a Service alarm and shows Off if there is no Service alarm Display Readings On or Off Filter alarm Read Only Filter Alarm Shows On if there is a Filter alarm and shows Off if there is no Filter alarm Display Readings On or Off Fan lock alarm Read Only Fan Lock Alarm Shows On if there is a problem detected on ...

Page 63: ...Shows if Frost Alarm active or not Display Readings On or Off Recovery status Read Only Recovery Status Shows if Frost Alarm active or not Display Readings On or Off Local motion Read Only Local Motion Shows if Frost Alarm active or not Display Readings Motion or No Motion Deh status Read Only Dehumidification Status Shows if dehumidification is active or not Display Readings On or Off Room humidi...

Page 64: ...fig Analog Analog SERVICE VIEW 6 9 PARAMETER DETAILS Configuration parameters Default Value Significance and Adjustments UO9 config Read Only UO9 Configuration Shows Analog Binary Relay RC or Relay RH UO10 config Read Only UO10 Configuration Shows Analog Binary or Relay RC UO11 config Read Only UO11 Configuration Shows Analog or Binary UO12 config Read Only UO12 Configuration Shows Analog or Binar...

Page 65: ... 7 9 PARAMETER DETAILS Configuration Parameters Default Value Significance and Adjustments UI19 type Read Only UI19 Input Type Shows Thermistor Binary or Voltage UI20 type Read Only UI20 Input Type Shows Thermistor Binary or Voltage UI22 type Read Only UI22 Input Type Shows Thermistor Binary or Voltage UI23 type Read Only UI23 Input Type Shows Thermistor Binary or Voltage UI24 type Read Only UI24 ...

Page 66: ... Only CO2 Module Shows if CO2 value is being ready from internal sensor wired sensor or CO2 sensor module Display Readings None Local Error and Wireless CO2 err code Read Only CO2 Error Code Error code 0x0001 shows if there is an error with the sensor CO2 level Read Only CO2 Level Shows CO2 level in ppm Display Readings 0 to 2000 CO2 FW rev Read Only CO2 Firmware Revision Shows the Firmware versio...

Page 67: ... 0 0 VT86xxUxx xxx The Device Name BACnet name consists of the model number followed by the COM address MAC address The BACnet name can be changed via the BACnet front end and the new name appears on the above screen For example when a VT8600U5B00 Room Controller with a MAC address of 41 is connected to a network its default Device Name is VT8600UxB00 41 and its default BACnet Device ID is 86041 ...

Page 68: ...Test Outputs Screens ...

Page 69: ...rridden the command is cancelled after 1 minute of screen inactivity auto exit to main screen or when page is exited Note 2 Use high caution when manually enabling outputs so as to not cause damage to equipment It is the responsibility of the Installer or Service Contractor to maintain a safe operation environment during usage Note 3 These parameters can also be changed via BACnet and the changed ...

Page 70: ...ity array 1 16 includes a value the displayed state background shows in red 2 When toggling a value on the screen the output directly energizes according to the selected value 3 After any output state gets modified all overrides get cancelled after 1 minute of button inactivity or if you scroll from one screen to another screen CASE A screen 2 2 display is dependent on Control type configuration I...

Page 71: ...Language Selection Screens ...

Page 72: ...abled 3 4 Language Selection Indonesian Polish Norwegian Disabled Disabled Disabled Italian Disabled Japanese Disabled Portuguese Disabled 4 4 Language Selection Slovak Disabled Swedish Disabled Turkish Disabled LANGUAGE SELECTION 1 4 TO 4 4 Only English French Spanish Chinese and Russian are enabled by default and are accessible to users cycling through languages on the display settings menu scre...

Page 73: ...Schedule Screens ...

Page 74: ...cs com Tel 514 321 5660 Fax 514 321 4150 028 0427 11 October 2018 Options Schedule Menu Clock Schedule Clock settings Schedule settings Options settings Note The Clock Schedule Menu screen is directly accessible from the main set up screen Clock Schedule Menu ...

Page 75: ...alue AM PM Time Format Current time display format Choice between 12 hour AM PM time format or 24 hour time format Note Changing the value of this parameter automatically changes the format of the displayed value of the time parameter Choices AM PM or 24 Hours Time Default value current time at power up Time Standard time display 12 hour AM PM or 24 hour format determined by the Time Format parame...

Page 76: ...cupied status The Room Controller can use the appropriate setpoints back and forth up to three times per day PARAMETER DETAILS Configuration Parameters Default Value Significance and Adjustments Occupied 1 3 Default value None Occupied 1 3 Defines a time when the Room Controller is automatically set to use the Occupied setpoint Note There are 3 separate Occupied parameter entries Range 00 00 24 00...

Page 77: ...meters Default Value Significance and Adjustments Occupancy cmd Default value Local occ Occupancy Command Loc occ occupancy is determined by local sequences either PIR or schedule as configured under Occ source Occupied force occupied mode Unoccup force unoccupied mode Choices Loc occ Occupied or Unocc Schedule type Default value 7 days Schedule Type 7 days Independent scheduling identified by day...

Page 78: ...ADR Screens ...

Page 79: ...hed status Default value Off Read Only Load Shedding Status Displays the status of the Load Shedding Demand whether it is active On or not Off The Load Shedding status is On when the Permission is On Shed demand is On and the Shed Override is Off Off Load Shedding Demand is not activated On Load Shedding Demand is activated Display Readings On or Off Shed demand Default value Off Read Only Load Sh...

Page 80: ...shedding offset The heating setpoint is calculated as follows Occupied heating setpoint occupied heating setpoint Load shedding offset Choices 4 F to 10 F 2 C to 5 5 C Shed override Default value Off Read Only Load Shedding Override Displays whether the user disabled the ADR request by the utility company When the demand shed is applied the user can override the ADR settings from its original setp...

Page 81: ...Wireless Screens ...

Page 82: ...514 321 4150 028 0427 11 October 2018 Wireless Ecosystem Alarms Configuration Device Groups Alarms IO Wireless Menu Options The Wireless screen shows only if the optional ZigBee communication module is installed Up to 11 devices can be added to the Device Groups for each Room Controller ...

Page 83: ...ler to pair with a ZigBee device Value must be set to On to pair with initial device and then set to Off if user wants to prevent additional ZigBee devices from joining the network Changing this value to Off on the Coordinator prevents any new ZigBee devices from joining the network Permit join can be On Off when the Room Controller is a coordinator however the parameter is read only when the Room...

Page 84: ...ON Once the timer elapses no devices will be able to join the network NOTE Permit Join parameter must be set to On to enable this feature Range 0 or 180 minutes Paired devices Default value 0 Read Only Paired ZigBee Devices Shows the number of Zigbee devices currently paired with the Room Controller A maximum of 10 ZigBee Pro devices and 1 ZigBee Green Power device can be paired with each Room Con...

Page 85: ...gnificance and Adjustments Door installed Default value No Read Only Door Contact Installed Shows if Door sensor is installed Display Readings Yes or No Win installed Default value No Read Only Window Contact Installed Shows if Window sensor is installed Display Readings Yes or No Water installed Default value No Read Only Water Leak Sensor Installed Shows if Water Leak sensor is installed Display...

Page 86: ...ce list Water Water Leak sensor installed Choices None Window Door Motion Status Remove and Water Comm status Default value Offline Read Only Communication Status Shows if device is communicating with Room Controller Not paired Device not paired Online Device paired and online Offline Device paired but offline Invalid Device was paired and Room controller detected a communication error selected fu...

Page 87: ...Status Shows the following status of ZigBee end device None N A Closed Door and Window Sensors Opened Door and Window Sensors No Motion Motion Sensor only Motion Motion Sensor only Normal Water Leak Sensor only Leak Water Leak Sensor only Temperature Read Only Wireless Device Temperature Displays the temperature value received from the wireless device If the wireless device does not support temper...

Page 88: ...us Default value Off Read only Communication Status Shows communication statues between Room Controller and ZigBee Green Power device Not paired Room Controller is not paired with any wireless ZigBee Green Power device Online Shows Room Controller is communicating with wireless ZigBee Green Power device Invalid Room Controller is communicating with device not using ZigBee Green Power protocol Offl...

Page 89: ...ue None Read only Wireless Device Battery Shows current status of battery in wireless device Display Readings None Normal or Low Address Read only Wireless Device Address Shows unique address of ZigBee end device Temperature Read only Wireless Device Temperature Shows current temperature on Room Controller display screen as detected by device ...

Page 90: ...able Default value Off Temperature Alarm Enabled Enables wireless device to alert Room Controller if temperature value reaches defined value in a particular Choices On or Off Threshold Default value 40 F 4 5 C Temperature Alarm Threshold Sets alarm threshold for system temperature sensors Range 32 to 45 F 0 to 7 C Hysteresis Default value 4 F 2 C Temperature Alarm Hysteresis Choices 0 to 10 F 0 to...

Page 91: ...eless paired device has a low battery status On or no paired device has low battery Off Choices On or Off Water leak Read Only Water Leak Sensor Status Shows if any water sensor paired device has detected a water leak On or no leak detected in any of the water sensor paired devices Off Choices On or Off Low temp Read Only Low Temperature Alarm Shows if any water sensor paired device has detected a...

Page 92: ...LUA Screens ...

Page 93: ...ive Halted LUA script stopped and not active Idle LUA script is running but not currently performing any actions Waiting LUA script running and waiting for a response Uploading LUA script currently unloading from Room Controller Loading LUA script currently loading to Room Controller Display Readings Idle Loading Running Waiting Halted Unloading Program error Default value No error Read Only Progr...

Page 94: ... The value s of this parameter depends on what is assigned to it using the LUA script function Parameter E Default value 0 AV29 Default value can be changed by user The value s of this parameter depends on what is assigned to it using the LUA script function Parameter F Default value 0 AV30 The value s of this parameter depends on what is assigned to it using the LUA script function Parameter defi...

Page 95: ...SECTION 3 Appendix ...

Page 96: ...ctions between the terminals of the VT7300 series and the VT8600 series Consult the table below to verify the appropriate terminal when replacing a VT7600 Room Controller with a VT8600 Room Controller VT7000 VT8600 Terminal name Terminal ID Terminal name Terminal ID Binary Input 1 BI1 Universal Input 16 UI16 Binary Input 2 BI2 Universal Input 17 UI17 Universal Input 3 UI3 Universal Input 19 UI19 S...