CONFIGURATION 7/11
7/11 Configuration
Min fresh air
Econo min pos
0 %
Max CO2
Min CO2
Max fresh air
100 %
800 ppm
0 CFM
Econo max pos
0 CFM
1200 ppm
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Econo min pos
Default value
: 0%
Economizer Minimum Position
Minimum Outside Air damper position when Room Controller is in Occupied, Standby
or Override mode and Fan status is ON. If Room Controller is in Unoccupied mode
and/or the Fan is Off, Outside Air damper position goes to 0%.
Range:
0% to 100%
Econo max pos
Default value:
100%
Economizer Maximum Position
Maximum Outside Air damper position when Room Controller is in Occupied,
Standby or Override mode and Fan status is ON. This is valid only for Economizer,
CO
2
and Airflow functions.
Range:
0% to 100%