Modbus Network Settings
Modbus network screen shows when Modbus is selected in wired protocol parameter.
1/1 Modbus Network
Parity
None
Network units
SI
Baud rate
19200
COM address
254
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Comm address
Default value:
254
Communication Address
Valid address range is set at 1 to 247 and each Modbus device must have a unique
address. Other values not recommended for Modbus.
Default value of 254 disables Modbus communication for the Room Controller.
Range
: 0 to 254
Network units
Default value:
SI
Measurement Units
Network units transmitted over the BACnet network.
NOTE:
Use the Temperature scale parameter to change the display units locally on
the Room Controller.
Imperial
: network units shown as Imperial units.
SI
: network units shown as International Metric units.
Choices
: Imperial or SI
Baud rate
Default value:
19200
Modbus Baud Rate
Automatically detects Modbus baud rate.
Choices
: 57600, 38400, 19200, 9600, and 4800
Parity
Default value:
Even
Parity
Determines how the parity bit of the character’s data frame is set to detect any errors
in the sent/receives frame.
Choices
: None, Odd and Even
Summary of Contents for VT8600 Series
Page 3: ...SECTION 1 Introduction ...
Page 6: ...HMI Display and Set up ...
Page 10: ...SECTION 2 Customized Screens ...
Page 17: ...Network Screens ...
Page 25: ...Configuration Screens ...
Page 48: ...Setpoints Screens ...
Page 53: ...Display Screens ...
Page 58: ...Service View Screens ...
Page 68: ...Test Outputs Screens ...
Page 71: ...Language Selection Screens ...
Page 73: ...Schedule Screens ...
Page 78: ...ADR Screens ...
Page 81: ...Wireless Screens ...
Page 92: ...LUA Screens ...
Page 95: ...SECTION 3 Appendix ...