4/11 Configuration
Frost protec.
Heating CPH
Cooling CPH
Off
4
4
BO1 aux. config
NO
Anti short cycle
2 min
64 °F
Min sup. heat
CONFIGURATION 4/11
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Cooling CPH
Default value:
4 CPH
Cooling Output Cycles Per Hour
CPH is used to “modulate” On/Off outputs controlling equipment such as
compressors. When the Room Temperature is within the Proportional Band, the
output performs 3 or 4 CPH. A higher CPH represents a higher accuracy of control at
the expense of wearing mechanical components faster.
Note
: The CPH does not limit the number of Cycles Per Hour. It is limited by the “Anti
short cycle” parameter. 4 CPH is typical for Rooftop applications.
Range
: 3 to 4 CPH
Heating CPH
Default value:
4 CPH
Heating Stages Cycles per Hour
CPH is used to “modulate” On/Off outputs controlling equipment such as
compressors. When the Room Temperature is within the Proportional Band, the
output performs 3 to 8 CPH. A higher CPH represents a higher accuracy of control at
the expense of wearing mechanical components faster.
For multi-stage models, heat cph applies to W1 & W2. A CPH value between 6 - 8 is
recommended for applications with electric heating. For gas applications set CPH to 4
and for oil applications set CPH to 3.
Range
: 3 to 8 CPH
Summary of Contents for VT8600 Series
Page 3: ...SECTION 1 Introduction ...
Page 6: ...HMI Display and Set up ...
Page 10: ...SECTION 2 Customized Screens ...
Page 17: ...Network Screens ...
Page 25: ...Configuration Screens ...
Page 48: ...Setpoints Screens ...
Page 53: ...Display Screens ...
Page 58: ...Service View Screens ...
Page 68: ...Test Outputs Screens ...
Page 71: ...Language Selection Screens ...
Page 73: ...Schedule Screens ...
Page 78: ...ADR Screens ...
Page 81: ...Wireless Screens ...
Page 92: ...LUA Screens ...
Page 95: ...SECTION 3 Appendix ...