88
Viconics Technologies Inc.
www.viconics.com
|
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0427-11
October 2018
6/7 Configuration
Language
English
Units
°C
Low backlight
60 %
Night backlight
5 %
RH display
Disable
Device Green Power
Function
None
Battery
None
Address
0xXXXX
Comm. status
Off
Temperature
XX °F
PARAMETER DETAILS
Configuration Parameters Default Value
Significance and Adjustments
Function
Default value:
None
ZigBee Device Function
Shows presence of installed ZigBee Green Power device. Only 1 ZigBee Green
Power device can be paired to each Room Controller.
None:
No device paired to Room Controller
Remove:
Removes device from Device Green Power group
T, rH:
Temperature and Humidity sensor paired to Room Controller
T, rH, CO
2
: CO
2
sensor paired to Room Controller
Choices:
None, Remove, T, rH or T, rH, CO
2
Comm. status
Default value:
Off
Read only
Communication Status
Shows communication statues between Room Controller and ZigBee Green Power
device.
Not paired
: Room Controller is not paired with any wireless ZigBee Green Power
device.
Online
: Shows Room Controller is communicating with wireless ZigBee Green Power
device.
Invalid
: Room Controller is communicating with device not using ZigBee Green Power
protocol.
Offline
: Shows Room Controller is not communicating with wireless ZigBee Green
Power device.
Paired
: Room Controller is paired with wireless ZigBee Green Power device but there
is no wireless communication between the Room Controller of the device.
Display Status
: Not paired, Online, Invalid, Offline and Paired
Device Green Power
This screen is a subset of the Ecosystems screen and shows data for a paired Zigbee Green Power device. The temperature
parameter is only visible for ZigBee devices capable of measuring temperature readings.
NOTE:
This screen is only visible when the Room Controller is paired with a ZigBee Green Power device.
Summary of Contents for VT8600 Series
Page 3: ...SECTION 1 Introduction ...
Page 6: ...HMI Display and Set up ...
Page 10: ...SECTION 2 Customized Screens ...
Page 17: ...Network Screens ...
Page 25: ...Configuration Screens ...
Page 48: ...Setpoints Screens ...