Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
96
Load Connections to Single Voltage Distribution Panels
Figure 38:
List AA: +24V Distribution Panel (with Return Busbar) and List AB: +24V Distribution Panel
(without Return Busbar), (24) Bullet/TPS/TLS Circuit Breaker/Fuse Positions
Figure 39:
List AC: +24V Distribution Panel (with Return Busbar) and List AD: +24V Distribution Panel
(without Return Busbar), (4) GJ/218 Circuit Breaker Positions
+24VDC Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply or
order additional hardware)
Maximum Lug Width: 0.625 inches.
Return Busbar
(not included with List AB)
Observe proper
polarity when making
load connections.
WARNING!
Caution: A 100 A circuit breaker or fuse SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
A 175 A or greater circuit breaker SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
+24VDC Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
3/8-16 Captive Nuts on 1” Centers
(Customer must supply or order additional hardware)
Maximum Lug Width: 1.375 inches.
Return Busbar
(not included with List AD)
Observe proper
polarity when making
load connections.
WARNING!
For an 800A circuit breaker,
continuous load must not exceed 600A.