Installing Converter Output Cables
Rear
588705201 Module Mounting Shelf
or Top Shelf in 588705202, 588705203,
or 588705204 Shelf Assembly
Connect /–48/ jumpers here.
Assembly order is: lug, 1/4" flat washer,
1/4" lock washer, 1/4-20 nut.
Torque to 84 in-lbs.
Rear
588705200 Expansion
Module Mounting Shelf
Connect /–48/ jumpers here.
Assembly order is: lug, 1/4" flat washer,
1/4" lock washer, 1/4-20 nut.
Torque to 84 in-lbs.