NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
102
Figure 50:
List DC: +24V/-48V Distribution Panel,
(9) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and
(12) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)
Figure 51:
List DD: +24V/-48V Distribution Panel,
(5) +24V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar) and
(16) -48V Bullet/TPS/TLS Circuit Breaker/Fuse Positions (with Return Busbar)
Load
Connections
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
-48V Distribut
ion
+24V Distribut
ion
Observe proper
polarity when making
load connections.
WARNING!
Caution: A 100 A circuit breaker or fuse SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
A 175 A or greater circuit breaker SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.
Load
Connections
-48V Distribut
ion
+24V
Distributio
n
Load Return
Connections
LOAD AND LOAD RETURN CONNECTIONS
1/4-20 Studs on 5/8” Centers
(Customer must supply
or order additional
hardware)
Maximum Lug Width:
0.625 inches.
Observe proper
polarity when making
load connections.
WARNING!
Caution: A 100 A circuit breaker or fuse SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
A 175 A or greater circuit breaker SHALL HAVE an empty mounting
position between it and any other overcurrent protective device.