Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
65
Connections to Field Expansion Module Mounting Assembly
The field expansion module mounting assembly provides separate AC input connections for each rectifier.
Circular openings are provided in the side panels (side feed) and rear covers (rear feed) of the module
mounting assembly for AC input and AC input equipment-grounding conductors. The openings accept 3/4"
inch conduit fittings. AC input wiring should be provided to all mounting positions intended for rectifiers,
including currently unused positions. This wiring will ease future installation of rectifiers to meet increased load
requirements.
NOTE!
A grounding conductor must be provided with each conduit.
Procedure
as these procedures are performed.
Accessing Connections and Routing Wire
1.
Remove the two AC input access covers from the rear of the module mounting assembly by first
removing the screws that secure them.
2.
Install conduit fittings in the side or rear openings as required. Plug buttons are provided, and must be
installed in the openings not being used.
3.
Route wiring into the shelf through the previously installed conduit fittings.
Making AC Input Connections
NOTE!
Module mounting positions are lettered left to right as viewed from the front of the shelf, A-D in
the top row and E-H in the bottom row.
NOTE!
If module mounting positions B, C, F, and G are intended solely for DC-DC Converter installation
(Converter Option must be installed), AC input connections to these positions are not required.
1.
Make AC input connections as shown in
. Connect each wire by inserting the stripped end
into the wire opening, and then tightening the screw. Recommended torque is 10 in-lbs.
208/240 VAC Service Type:
•
Line to Line:
Connect Line 1 to Terminal 1.
Connect Line 2 to Terminal 2.
•
Line to Neutral:
Connect Line to Terminal 1.
Connect Neutral to Terminal 2.