Procedure
1.
To Select a Sub-Menu:
Press the UP and DOWN keys to highlight the desired sub-menu. Press the ENT key to enter the
selected sub-menu.
2.
To Select a User:
To select a User, use the UP and DOWN keys to move the cursor to the Select User field. Press ENT.
Use the UP and DOWN keys to select a User previously programmed into the NCU. Press ENT to select
the User. Note that only Users programmed into the NCU are shown. Users are programmed via the
Web Interface. The default User is admin.
3.
To Enter a Password:
To enter a password, use the UP and DOWN keys to move the cursor to the Enter Password field. Press
ENT. Use the UP and DOWN keys to choose a character. Press ENT to accept and move to the next
character. Continue this process until all characters are entered. Press ENT again to accept the
password. The default password is 640275.
4.
To Change a Parameter:
Press the UP and DOWN keys to move up and down the list of parameters. Press ENT to select the
parameter. Press the UP and DOWN keys to change the parameter. Press ENT to make the change.
Press ESC to cancel the change.
shows the menu navigation for some basic settings. Refer to the separate NCU Manual
(UM1M830BNA) supplied with your power system for complete Local Display menus.
Table 13:
NCU Basic Settings Menu Navigation
Parameter
Menu Navigation
Date
Main Menu / Settings Icon / Sys Settings / Date.
Time
Main Menu / Settings Icon / Sys Settings / Time.
IP Communications
Parameters
(IP address, subnet mask
address, gateway address)
Main Menu / Settings Icon / Comm Settings / enter parameters.
Float Voltage
Main Menu / Settings Icon / Batt Settings / Charge / Float Voltage.
Equalize Voltage
Main Menu / Settings Icon / Batt Settings / Charge / EQ Voltage.
Battery Capacity
Main Menu / Settings Icon / Batt Settings / Batt1 Settings or Batt2
Settings / Rated Capacity.
Battery Charge Temperature
Compensation
Main Menu / Settings Icon / Batt Settings / Temp Comp (enter
parameters).
Rectifier Current Limit
Main Menu / Settings Icon / Rect Settings / Current Limit (set to
enabled) then set Curr Limit Pt.
Over Voltage Alarm 1
Main Menu / Settings Icon / Other Settings / Over Voltage 1.
Over Voltage Alarm 2
Main Menu / Settings Icon / Other Settings / Over Voltage 2.
Under Voltage Alarm 1
Main Menu / Settings Icon / Other Settings / Under Voltage 1.
Under Voltage Alarm 2
Main Menu / Settings Icon / Other Settings / Under Voltage 2.