Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
133
10.
When you have finished selecting identification numbers for all rectifiers, repeatedly press ESC to return
to the Main Menu.
11.
Navigate to and select “Manual” (ENT) / “Rectifier” (ENT) / “All Rect Ctrl” (ENT).
12.
Navigate to “Confirm ID/PH”. Press ENT. “Yes” highlights.
13.
Press ENT to select the operation. Press ENT again to confirm.
NOTE!
Check you numbering to be sure it is correct. If there where conflicts in your numbering,
rectifiers with conflicts will be assigned the next available sequential number.
14.
Return to the Main screen by repeatedly pressing ESC (escape).
Configuring the ACU+ Identification of Converter Modules
When converters are all installed prior to applying power and starting the system, the order in which the ACU+
identifies the converters is by serial number (lowest serial number is Conv 1, next lowest is Conv 2, etc.).
If you prefer the ACU+ to identify the converters by position in the system, perform the following procedure.
Procedure
1.
With the Main screen displayed, press ENT to go to the Main Menu. Navigate to and select “Settings”
(ENT).
2.
If a password screen opens, a password must be entered to allow the User to make adjustments. If a
password was previously entered and has not yet timed out, skip this step and proceed to step 3).
Otherwise, to enter a password, with the cursor at the User Name field (default is “Admin”), press the
down arrow key to move cursor down to the password line. Press ENT. “0” is highlighted. Press the up
arrow key once to change the “0” to”1” (default password is “1”), then press ENT twice.
(
Note:
If you
have been assigned a unique User Name and password, follow this procedure to enter these.)
3.
With the Settings menu screen displayed, navigate to and select “Converter” (ENT).
4.
Navigate to “Conv #” (# is used here to represent the converter identification number). Press ENT.
The converter # menu screen is displayed, and the green LED on one converter starts flashing. This is
the converter currently identified by the ACU+ as converter #. (If this is not the converter you want,
press ESC to return to converter menu screen and select a different converter.)
5.
Navigate to and select “Set Conv ID”. Press ENT. Use the up or down keys to change the ACU+
identification number for the flashing converter. Press ENT.
6.
Press ESC to return to converter menu screen.
7.
Navigate to and select the next converter.
8.
Repeat steps 4) through 7) for each of the remaining converters in the system.
9.
When you have finished selecting identification numbers for all converters, repeatedly press ESC to
return to the Main Menu.
10.
Navigate to and select “Manual” (ENT) / “Converter” (ENT) / “All Conv Ctrl” (ENT).
11.
Navigate to “Confirm ID”. Press ENT. “Yes” highlights.
12.
Press ENT to select the operation. Press ENT again to confirm.