Figure 12:
Installing a Bullet Nose Type Fuseholder and TPS/TLS Fuse
Installing Bullet Nose Type Circuit Breakers
CAUTION!
A 100 A circuit breaker or fuse SHALL HAVE an empty mounting position between it and
any other overcurrent protective device. A 175 A or greater circuit breaker SHALL HAVE an empty
mounting position between it and any other overcurrent protective device.
Refer to SAG581127000 for any other restrictions.
Refer to the following procedure and install appropriately sized bullet nose type circuit breakers into the proper
mounting positions in the distribution cabinet.
Procedure
NOTE!
as this procedure is performed.
1.
Open the distribution cabinet’s front door by turning the latch in the counterclockwise position.
2.
Ensure that the circuit breaker is in the OFF position and is of the correct rating. Orient the circuit
breaker as shown in
. Insert the terminals on the rear of the circuit breaker into their
Fuseholder Assembly
Longer Side
to the Bottom
Shorter Side
to the Top
Fuse Carrier
Fuseholder Body
TPS/TLS Fuse
Polarizing Keyway
Matches Key on
Bottom of Fuse Carrier
Fuseholder Assembly
Exploded View
Fuseholder Assembly (P/N 117201) includes
body & carrier, alarm fuse, and alarm fuse safety cover.
Insert these terminals
into corresponding sockets
on distribution panel.
GMT-X
Safety Fuse Cover
(Replacement
P/N 248898700)
GMT-18/100A
Alarm Fuse
(Replacement
P/N 248610301)