Vertiv
|
NetSure 710 Series Installation Manual (IM581127000)
|
Rev. U
74
Table 5:
Programmable Digital Inputs – IB2 Board
Programmable
Digital Input
IB2
Pin No.
Factory
Wiring
Default Digital
Input Function
Customer Defined
Digital Input Function
1
J3-2
+
The digital inputs may
be preprogrammed for
specific functions and
have factory wiring
connected. Refer to the
configuration drawing
(C-drawing) supplied
with your system for
your system’s specific
configuration.
The digital inputs may
be preprogrammed for
specific functions.
Refer to the
configuration drawing
(C-drawing) supplied
with your system for
your system’s specific
configuration.
J3-1
–
2
J3-4
+
J3-3
–
3
J3-6
+
J3-5
–
4
J4-2
+
J4-1
–
5
J4-4
+
J4-3
–
6
J4-6
+
J4-5
–
7
J5-2
+
J5-1
–
8
J5-4
+
+24 VDC
ESTOP
J5-3
–
(to customer
ESTOP switch)
--
J5-5
not used
not used
not used
--
J5-6
NOTE!
+24V is factory wired to the Digital Input #8 (+) terminal for your convenience and function
predefined for ESTOP. Customer-furnished system ground applied to terminal Digital Input #8 (-)
activates the ESTOP function. The ESTOP function shuts down and locks out the rectifiers, opens the
LVD’s, and shuts down the converters. When the ESTOP signal is removed, LVD’s close (if battery
present) and converters restart. To restart the rectifiers; turn AC power to the rectifiers OFF, wait 30
seconds or more (until the LEDs on the module extinguish), then turn AC power to the rectifiers ON.