Vertiv™ XTE 601E Series Equipment Enclosures Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
88
Exiting the ECU maintenance mode. Maintenance Mode can be exited by closing the door or by depress the Audible
Alarm Cutoff / Maintenance / Reset pushbutton for more than 10 seconds.
Placing the ECU circuit breaker in the DC distribution shelf into the “ON” position.
Reconnecting power to the ECU by mating the in-line ECU power cable connectors.
12.
Monitor the ECU to make sure that the replacement fan is powered up and that it initializes, calibrates, and goes into steady
state.
13.
Close the enclosure front door.
14.
Replace the door padlock, if required.
17.7
Configured Equipment
Equipment from Vertiv and 3rd-party manufacturers may be furbished and factory-installed in the XTE 601E 84" equipment enclosure.
This may include equipment for DC power and distribution, AC power and backup (UPS), site management, RAN surge suppression,
DC voltage up conversion, fiber connectivity, etc.
Please consult Vertiv for available options and/or to have new customer-specific equipment integrated.