Vertiv™ XTE 601E Series Equipment Enclosures Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
52
Figure 12.1
Local Alarm Block Schedule (F2019015) (cont’d on next page)
Alarm Block
Location
Front door removed
in illustration for
clarity only.
R66 BLOCK# 1
POS
CLIP
#
ALARM
SOURCE
A
B
C
D
1
DOOR_INTRUSION
ECU/DOOR
SWITCH
BLU
2
1
BRN
2
FAILURE
DC POWER
SYSTEM
4
3
SURGE_SUPPRESSOR
LIGHTNING_ARRESTE R
SURGE
SUPPRESSOR
6
4
RECTIFIER_ FAILURE
DC POWER
SYSTEM
8
5
MU LTIPLE_
10
6
11
BATTE RY_DISCHARGE
LOW_VOLTAGE
12
7
13
14
8
15
DC_POWER_ FAILURE
16
9
17
GENERATOR_RUNN ING
GENER ATOR
18
10
19
20
11
21
GENER ATOR_FAILURE
22
12
23
HVAC_ FAILURE
HVAC/ECU
BLK
24
WHT
13
25
SMOKE_FIRE
26
14
27
HIGH_TEMP
T’STAT/ECU
VIO
28
YEL
15
29
TOWER_LIGH T
(REQUIRES FAA
NOTAM)
30
16
31
TOWER_L IGHT_SIDE
32
17
33
RRU_UP
DC/DC
CONVE RTER
34
18
35
RRU_POWER_ FAILURE
OVP SHELF
36
19
37
RRU_HIGH_HUMIDITY
38
20
39
RRU_INTRUSION
40
21
RUNNING
42
22
43
FIRE
DISCHARGE
44
23
45
FIRE
TROUBLE
46
24
LOW_TEMP
48
25
49
DEHYDR ATOR_ALARM
50