![Vertiv F2019015 Description And Installation Manual Download Page 85](http://html1.mh-extra.com/html/vertiv/f2019015/f2019015_description-and-installation-manual_1007965085.webp)
Vertiv™ XTE 601E Series Equipment Enclosures Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
77
16.4
High Temperature Alarm
The enclosure is equipped with a high-temperature alarm thermostat. The alarm setting is 65C.
16.5
Optimal Cooling Locations for Rack-Mount Equipment
The ideal cooling location in the equipment rack is RU's 10-19 (from bottom of EQ rack). But near-optimal cooling can be achieved in
any location RU's 1-19. See Figure 16.2.
Cooling can always be improved by closing off open areas in the EQ rack with blanking plates, to prevent recirculation of equipment
exhaust air directly back into the equipment intakes.
Figure 16.2 Cooling Zones (F2019016)
10 RU Ideal Cooling
9 RU Near-Optimal Cooling