Vertiv™ XTE 601E Series Equipment Enclosures Description and Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
48
10
DC Power
10.1
Safety Precautions
DANGER!
RISK OF ELECTRICAL SHOCK, GENERAL
All ground connections must be installed and verified prior to connecting any power cables (AC or DC) and turning-up of
enclosure.
When connecting any discrete power connection, make the connection first with the ground/return and break last with
ground/return.
Remove rings, metallic wrist bands, or bracelets, etc.
Do not install equipment showing any physical damage.
DANGER!
RISK OF ELECTRICAL SHOCK, DC
An OFF Battery Switch / Breaker does not isolate the batteries, nor do the batteries have a protective fuse. Thus, handle
accordingly and use only insulated tools when working around batteries or any DC potential.
In addition, be sure that all connection points have been de-energized.
GMT fuses can produce sparks during interruption or clearing of a fault, so only use Bussman GMT fuses provided with safety
caps.
10.2
General
Refer to “Site Ground” on page 28 and “Grounding the Enclosure” on page 42 for information on site and enclosure ground
respectively.
10.3
DC Power Cabling Color Scheme
On the enclosure, the DC power cabling color scheme is:
•
BLACK is return
•
RED or BLUE is –48 VDC Power.
10.4
DC Power System
The enclosure may include a DC power system and distribution.
Refer to the documentation furnished with the power system.