40
6.
Tap enclosure anchors loosely into position, leaving about 3/4" above the enclosure’s mounting surface. If a battery box is
installed, align and loosely set the rear set of anchors first, then go to the front of the lowest battery box. Remove the L-
shaped covers that hide the front anchor positions (refer to Figure 6.7) and tap enclosure anchors loosely into position.
7.
Use a level and the shims supplied with the enclosure accessory kit to level the enclosure as required. Slots in shims must be
aligned with enclosure mounting holes to work properly for seismic Zone 4 applications.
8.
Open and close the front door and verify it will open, close, and lock properly. If not, adjust the shims, until the door functions
properly.
9.
Complete installation of enclosure anchors. If present, re-install the L-shaped anchor covers in the lowest battery box (refer
to Figure 6.7).
10.
When the enclosure is secured, remove the slings, the tagline, and the lifting eyebolts.
11.
Remove the rear access panels and put to the immediate side. See “Removing/Installing Rear Access Panels” on page 22.
12.
If leaving the site or enclosure unattended:
•
Put the accessory kit back into the enclosure.
•
Install all rear access panels.
•
Close and secure the front door.
•
If storing for more than one month, review requirements of long-term storage.
ALERT!
If the enclosure will not be powered up for an extended period, place a heat source, such as a 100 W light bulb inside
the enclosure to prevent condensation.