4.5.2
COOLING OF STANDALONE AC DRIVES (FR10 TO FR11)
B
C
A
Fig. 16: The minimum clearances around the AC drive
A. The minimum distance to the side walls
or adjacent components
B. The minimum distance from the top of
the cabinet
C. Free space in front of the cabinet
Table 21: The minimum clearances around the AC drive
Installation space dimensions [mm]
Installation space dimensions [in]
A
B
C
A
B
C
20
200
800
0.79
7.87
31.50
Table 22: The necessary quantity of cooling air
Drive type
The quantity of cooling air [m
3
/h]
The quantity of cooling air [CFM]
0385 5-0520 5
0261 6-0416 6
2600
1530
0590 5-0730 5
0460 6-0590 6
3900
2295
For more information on the power losses based on the switching frequency, see Chapter 11
Appendix 1.