Expose the shield of all cables to make a 360-
degree connection with the grounding clamp for
cable shield.
10 Attach the cable entry plate, and then the cable
cover.
Make sure that the control cables or the cables of
the AC drive are not caught between the frame and
the cable cover.
11 For FR8, attach the cover of the drive (unless you
want to make the control connections first).
Table 38: Tightening torques of the terminals
Frame
Type
Tightening torque:
the mains cable and motor cable
terminals
[Nm]
lb-in.
FR8
0168 2-0205 2
0168 5-0205 5
40
354
FR9
0261 2-0300 2
0261 5-0300 5
0125 6-0208 6
40
354
5.7.3
FRAMES FR10-FR11
For more information on how to install the cables for frames FR10 and larger, see Vacon
NXP Enclosed Drives User Manual.
POWER CABLING
VACON · 69