8.3.2
THE RUN TEST WITHOUT THE MOTOR
Do either Test A or Test B:
Test A: Controls from the control terminals
1
.
Turn the Start/Stop switch to ON position.
2
.
Change the frequency reference (potentiometer).
3
.
Do a check in the Monitoring menu M1 that the value of Output frequency changes the
equivalent quantity to the frequency reference.
4
.
Turn the Start/Stop switch to OFF position.
Test B: Control from the control keypad
1
.
Change the control from the control terminals to the keypad. For the instructions, see
Chapter 7.6.1.1 Changing the control place.
2
.
Push the Start button on the keypad.
3
.
Go to the Keypad control menu (M3) and Keypad Reference submenu (Chapter 7.6.2 The
keypad reference submenu (P3.2)). To change the frequency reference, use the Browser
buttons.
4
.
Do a check in the Monitoring menu M1 that the value of Output frequency changes the
equivalent quantity to the frequency reference.
5
.
Push the Stop button on the keypad.
8.3.3
START-UP TEST
Do the start-up tests without the motor connected to the process, if possible. If this is not
possible, make sure that it is safe to do each test before you do it. Make sure that the other
workers near you know that you do the tests.
1
.
Turn the supply voltage off and wait until the drive stops. See Chapter 8.2 Commissioning
of the drive, step 5.
2
.
Connect the motor cable to the motor and to the motor cable terminals of the frequency
converter.
3
.
Make sure that all Start/Stop switches are in Stop positions.
4
.
Turn the mains switch ON.
5
.
Do again the Run test A or B, see Chapter 8.3.2 The Run test without the motor.
8.3.4
IDENTIFICATION RUN
Make the Identification Run. The Identification Run helps to tune the motor and drive related
parameters. It is a tool that you can use in commissioning to find the best possible
parameter values for most drives. The automatic motor identification calculates or measures
the necessary motor parameters for the best possible motor and speed control. For more
information on the Identification Run, see All in One Application Manual, parameter ID631.
8.3.5
CONNECTING THE MOTOR TO THE PROCESS
If you did the start-up test without the motor connected, connect the motor to the process.
•
Before you do the tests, make sure that it is safe to do each test before you do it.
•
Make sure that the other workers near you know that you do the tests.
•
Do the Run test A or B, see Chapter 8.3.2 The Run test without the motor.
COMMISSIONING AND ADDITIONAL INSTRUCTIONS
VACON · 123