Table 53: The power ratings of Vacon
®
NX AC drives in mains voltage 208-240V, 50/60 Hz, 3~
Frame
Drive
type
Loadability
Motor shaft power
Low *
High *
Max
current
I
s
2 s
230 V mains
208-240 V mains
Continu
ous
current
I
L
[A]
10%
over-
load
current
[A]
Continu
ous
current
I
H
[A]
50%
over-
load
current
[A]
10%
over-
load
40°C
(104°F)
[kW]
50%
over-
load
50°C
(122 °F)
[kW]
10%
over-
load
40°C
(104°F)
[hp]
50%
over-
load
50°C
(122 °F)
[hp]
FR4
0003*
3.7
4.1
2.4
3.6
4.8
0.55
0.37
0.75
0004
4.8
5.3
3.7
5.6
7.4
0.75
0.55
1
0.75
0007
6.6
7.3
4.8
7.2
9.6
1.1
0.75
1.5
1
0008
7.8
8.6
6.6
9.9
13.2
1.5
1.1
2
1.5
0011
11.0
12.1
7.8
11.7
15.6
2.2
1.5
3
2
0012
12.5
13.8
11.0
16.5
22.0
3.0
2.2
-
3
FR5
0017
17.5
19.3
12.5
18.8
25.0
4.0
3.0
5
-
0025
25.0
27.5
17.5
26.3
35.0
5.5
4.0
7.5
5
0031
31.0
34.1
25.0
37.5
50.0
7.5
5.5
10
7.5
FR6
0048
48
52.8
31.0
46.5
62.0
11.0
7.5
15
10
0061
61.0
67.1
48.0
72.0
96.0
15.0
11.0
20
15
FR7
0075
75.0
83.0
61.0
92.0
122.0
22.0
15.0
25
20
0088
88.0
97.0
75.0
113.0
150.0
22.0
22.0
30
25
0114
114.0
125.0
88.0
132.0
176.0
30.0
22.0
40
30
FR8
0140
140.0
154.0
105.0
158.0
210.0
37.0
30.0
50
40
0170
170.0
187.0
140.0
210.0
280.0
45.0
37.0
60
50
0205
205.0
226.0
170.0
255.0
336.0
55.0
45.0
75
60
FR9
0261
261.0
287.0
205.0
308.0
349.0
75.0
55.0
100
75
0300
300.0
330.0
245.0
368.0
444.0
90.0
75.0
125
100
*) Only available for NXP range
NOTE!
The currents in given ambient temperatures (in 9.2 Vacon® NXS and NXP -
technical data) are achieved only when the switching frequency is the same or
smaller than the factory default.
VACON · 130
TECHNICAL DATA FOR NXS AND NXP
9
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205