Table 25: The cable and fuse sizes for Vacon
®
NXS and NXP, North America
Frame
Type
Fuse
Class(T/J)
Mains, Motor and
brake resistor
cable Cu [AWG]
Terminal cable size
Mains cable
terminal [AWG]
Grounding
terminal [AWG]
FR8
0140 2
0140 5
AJT175
3*2/0 AWG + 2 AWG
4 AWG - 3/0 AWG
Cu/Al
10 AWG - 3/0
AWG
0170 2
1)
0168 5
1)
AJT200
3*3/0 AWG + 1/0
AWG
3/0 AWG - 350kcmil
Cu/Al
10 AWG - 3/0
AWG
0205 2
0205 5
AJT250
3*30 2/0
AWG
3/0 AWG - 350kcmil
Cu/Al
10 AWG - 3/0
AWG
FR9
0261 2
1)
0261 5
1)
AJT300
3*35 3/0
AWG
2*(3*25 2/0
AWG)
3/0 AWG - 350kcmil
Cu/Al
10 AWG - 3/0
AWG
0300 2
1)
0300 5
1)
AJT400
2*(3*25 2/0
AWG)
3/0 AWG - 350kcmil
Cu/Al
10 AWG - 3/0
AWG
1)
Use cables with a +90 °C (194 °F) heat resistance to obey the UL standards.
VACON · 50
POWER CABLING
5
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205