Table 55: The power ratings of Vacon
®
NX AC drive in mains voltage 500-690 V, 50/60 Hz, 3~
Frame
Drive
type
Loadability
Motor shaft power
Low
High
Max
current
I
s
2 s
690 V mains
575 V mains
Continu
ous
current
I
L
[A]
10%
over-
load
current
[A]
Continu
ous
current
I
H
[A]
50%
over-
load
current
[A]
10%
over-
load
40°C /
104 °F
[kW]
50%
over-
load
50°C /1
22 °F
[kW]
10%
over-
load
40°C /
104 °F
[hp]
50%
over-
load
50°C /1
22 °F
[hp]
FR11
0460
460.0
506.0
385.0
578.0
693.0
450.0
355.0
450
400
0502
502.0
552.0
460.0
690.0
828.0
500.0
450.0
500
450
0590
590.0
649.0
502.0
753.0
904.0
560.0
500.0
600
500
NOTE!
The currents in given ambient temperatures (in 9.2 Vacon® NXS and NXP -
technical data) are achieved only when the switching frequency is the same or
smaller than the factory default.
The currents for FR10 to FR11 are valid at an ambient temperature of 40°C (104 °F) (except
for 0416 6 and 0590 6: currents are valid at an ambient temperature of 35°C (95 °F)).
9.1.4
OVERLOAD CAPABILITY
The low overload means that if 110% of the continuous current (I
L
) is necessary for 1 minute
each 10 minutes, the remaining 9 minutes must be approximately 98% of I
L
or less. This is to
make sure that the output current is not more than I
L
during the duty cycle.
IL
IL*110%
1 min
9 min
I
t
IL*110%
Fig. 32: Low overload
The high overload means that if 150% of the continuous current (I
H
) is necessary for 1
minute each 10 minutes, the remaining 9 minutes must be approximately 92% of I
H
or less.
This is to make sure that the output current is not more than I
H
during the duty cycle.