34/108
5
The 'Abnormal Safety Input State' alarm can be clear by recycling the power of the controller. It cannot clear by
'Fault Reset' command of Control word.
The voltage limits of Back-EMF according to the motor model of the product are as follows.
Table 4-6: Voltage Limit of Back-EMF.
Motor Model
42L
56L
STDF EC
70 V
70 V
4.3
Mode of operation
Currently activated Mode of operation display (6061h) decides the action of the controller.
Meaning for some bits of Control word (6040h) and Status word (6041h) Objects can be
decided by Mode of operation display (6061h).
Able to set selected operation mode by Mode of operation (6060h). Currently, activated
operation mode can be checked by the Mode of operation display (6061h).
Operation modes supported by the current controller are as follows.
Table 4-7: Supported operation modes.
Mode of operation
Description
1
6
8
Profile Position Mode
Homing Mode
Cyclic Synchronous Position Mode
4.4
Cyclic synchronous position mode
4.4.1 Definition
Cyclic Synchronous Position mode (CSP Mode) assigns target position to the controller by
Master’s operation
profile creation function through cyclic communication. Controller
internally executes position/velocity control with receipt of target position in each cycle.
To use CSP Mode of operation (6060h) Cyclic Synchronous Position Mode needs to be set.
Mode of operation display (6061h) is shown as Cyclic Synchronous Position Mode, Target
position transmitted from master: Object 607Ah: Target position is executed.