Configuring with Turck Safety Configurator and Rockwell Studio 5000
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
58
8.1.11
Application Example
Emergency Stop at FDI0/1 at C0 (64. OSSD),
Light grid (AOPD) at input FDI2/3 at C1 (63. OSSD),
Unsafe channels at C4 - C7 will be switched on permanently via the internal safety outputs (1. and
2. OSSD),
Output FDX4/5 at C2 (3. OSSD) is switched off if the emergency stop and/or the light grid are acti-
vated,
Output FDX6/7 at C3 (4. OSSD) is switched off, if output FDX4/5 is switched off,
. The
output state is transferred to the F-CPU.
Release of the complete safety function via a release bit in the F-CPU (3. OSSD),