![background image](http://html1.mh-extra.com/html/turck/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol/tbip-l-fdio1-2iol-series-tbip-l4-fdio1-2iol_instructions-for-use-manual_1181729073.webp)
65
2018/02
TBPN-L1
-FDIO1-2IOL- Saf
e
I/O
Switch-off FDX6/7 at C3 (4. OSSD), if output FDX4/5 is switched.
Output FDX6/7 has to switch off if output FDX4/5 (3. OSSD) switches off.
Delete "CIP Safety input" in OSSD 4.
Select the block "State of output switching element" from the Device library and place it at the
function input.
In the dialog box "State of output switching element x" select OSSD 3.
Fig. 40: State of output switching element OSSD 3 in OSSD 4
The state of 3. OSSD controls the output FDX6/7 in 4. OSSD.
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...