7
V01.0| 2017/04
TBPN-L1
-FDIO1-2IOL -
Standard IO-Link
2.2
Power supply of the IO-Link ports
2.2.1
Class A/B supply
Class A supply: pin 1 and pin 3,
Class B supply: pin 2 and pin 5
see also
NOTE
The two supply voltages are not galvanically isolated.
NOTE
Set the respective output (DXP 13 or DXP 15) in the process output data in order to acti-
vate the Class B supply, see
Process Output Data – IO-Link Master Channels (page 13)
.
2.2.2
Safe shutdown of IOL2 (at C7)
The IO-Link port at C7 is supplied via the internal safe output FSO 1.
This allows a safety-related shutdown of the port.
IO-Link port
Connector
Power supply
IOL1
C6
Vaux1
IOL2
C7
FSO 1 (clocked by test pulses)
NOTE
The IO-Link port at C7 is supplied via the internal safe output FSO 1.
Connected IO-Link devices must have a respectively high capacitance in order to tolerate
the test pulses of the safety output.