17
V01.0| 2017/04
TBPN-L1
-FDIO1-2IOL -
Standard IO-Link
Deactivate diagnostics
Influences the sending of IO-Link-Events from the master to the fieldbus. Depending on the parameteriza-
tion, the master transmits Events based on their priority to the fieldbus or not.
00
no
The master transmits all IO-Link Events to the fieldbus.
01
notifications
The master transmits all IO-Link Events to the fieldbus except for
IO-Link notifications.
10
notifications and
warnings
A
The master transmits all IO-Link Events to the fieldbus except for
IO-Link notifications and warnings.
11
yes
The master doesn't transmit any IO-Link Event to the fieldbus.
Process input data mapping
Optimization of the process data mapping for the used fieldbus:
The I/O-Link-data can be swapped depending on the used fieldbus in order to achieve an optimized data
mapping on the fieldbus side.
00
direct
A
The process data are not swapped.
(0x0123 4567 89AB CDEF)
01
swap 16 bit
The bytes are swapped per word.
(0x2301 6745 AB89 EFCD)
10
swap 32 bit
The bytes are swapped per double word.
(0x 6745 2301 EFCD AB89)
11
swap all
All bytes are swapped.
(0xEFCD AB89 6745 2301)
Process output data mapping
see: Process input data mapping
Vendor ID
0x0000 to
0xFFFF
Enter the IDs for the port configuration check.
Device ID
0x0000 to
0xFFFF
Name
Meaning
Value
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...