Setting IP Addresses
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
42
In "manual allocation", a client's IP address is assigned by the network administrator. In this case,
DHCP is only used to transmit the assigned address to the client.
6.4.3
Mode: PGM (500)
Switch position: 500
The PGM-mode enables access of the Turck DTMs to the device’s network settings.
HINWEIS
In the PGM-mode, all network settings (IP address, subnet mask, etc.) are send to the
device’s internal EEPROM and stored permanently.
6.4.4
Mode: PGM-DHCP (600)
Switch position: 600
The device sends DHCP-requests until an IP address is assigned by a DHCP server. The assigned IP
address is stored to the device and the DHCP-client is stopped. Even after a restart of the device, the
device sends no further DHCP-requests.
6.4.5
Resetting the IP Address (Safety Side), Switch Position "000"
By setting the DIP-switches to "000" followed by a voltage reset, the IP address of the safety side (left
side) is set to 192.168.1.254 (see
).
The IP address of the non-safety, right function unit remains unaffected
HINWEIS
Setting "000" is no operation mode! After having reset the IP address to the default values,
the device has to be set to another mode.
.
Summary of Contents for TBIP-L...-FDIO1-2IOL Series TBIP-L4-FDIO1-2IOL
Page 1: ...Your Global Automation Partner TBIP L FDIO1 2IOL Safety Block I O Module Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 118: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 2...